Single/Dual Action Manual Pull Stations
The Model XMS-S is a single action pull station in a plastic
housing that requires one action by the user to initiate the alarm.
The Model XMS-D is a double action pull station in a plastic
housing that requires two actions by the user to initiate an alarm.
The Model XMS-M is a single action pull station in a metal
housing that requires one action by the user to initiate the alarm.
These models are field installed addressable devices containing
advanced control panel communication technology. This
technology, which provides two-direction communication with the
control panel, produces an Intelligent Initiating Device.
Programming Instructions
Refer to Figure 1 to locate the programming holes which are
accessible through the rear cover.
Programming
Figure 1
Programming Holes Location
CAUTION: To prevent potential damage to the DPU DO NOT
connect an XMS to the DPU until the wire at terminal 1 is
removed. Follow the instructions in the DPU Manual, P/N
315-033260, to program the XMS to the desired address.
Record the device address on the label and attach it to the top
surface of the base. The XMS can now be installed and wired to
the system as shown in Figures 2, 3, and 4.
OPERATION
The XMS-S, XMS-D, and XMS-M manual stations operate with
the Desigo Fire Safety Modular/Cerberus PRO Modular via the
XDLC. These devices can be wired in either Isolation Mode or
Polarity Insensitive Mode Wiring). The XMS-S/XMS-M manual
station front cover has a recess pocket to pull down and locks in
position after the alarm is initiated. The XMS-D manual station
has an additional lever labeled "PUSH HERE THEN" to get
access to the front cover pocket to initiate the alarm.
A6V11856080_enUS_a
Holes
Rear Cover
firealarmresources.com
Resetting the Manual Station
To reset the stations, insert the Siemens T45 key provided into
the key lock and turn the key 10-15 degrees counter-clockwise as
the arrow shows. The cover will move upward to the normal
position. Rotate the key clockwise and remove key from the lock.
At Normal position the top of the Cover is flush with the top
surface of the Base. Reset the Fire Alarm Control Panel to clear
the alarm.
LED
Diagnostic LED provides visible indication of the manual station
status.
Normal: Green, LED flashes
Alarm: Red, LED flashes
Trouble: Amber, LED flashes. This will happen when the Front
Cover is removed from the Manual Station.
WIRING
NOTES:
1.
Recommended wire sizes: 18 AWG minimum, 14 AWG
maximum.
2.
When using shielded cable with or without metal
raceway, the shields must be grounded solely at the
point of origin, for example, at the control panel.
Line+
To next addressable
Line-
device
Line+
From control panel or
Line-
previous addressable device
Figure 2
Isolator Mode Wiring
Line 1
Line 2
Line 2
Line 1
Figure 3
Polarity Insensitive Mode Wiring
To next addressable
device
From control panel or
previous addressable
device

Advertisement

loading

Summary of Contents for Siemens XMS-SP

  • Page 1 Resetting the Manual Station The Model XMS-S is a single action pull station in a plastic To reset the stations, insert the Siemens T45 key provided into the key lock and turn the key 10-15 degrees counter-clockwise as housing that requires one action by the user to initiate the alarm.
  • Page 2 CAUTION: Do not overtighten the screws. Overtightening may distort the Base. Installation Instructions: Remove the cover. Insert the Siemens T45 key provided into the key lock and rotate key 90 degrees Figure 4 counter-clockwise. Remove the key. The cover can Mounting the XMS Series now be removed.
  • Page 3 In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art security concept. Siemens’ portfolio only forms one element of such a concept. You are responsible for preventing unauthorized access to your plants, systems,...
  • Page 4 Document ID A6V11856080_enUS_a P/N A5Q00072530 firealarmresources.com...

This manual is also suitable for:

Xms-dpXms-seXms-de