ESSER Panels
Tools 8000 Settings for ESCOM Panels
1. Select the Serial Interfaces tab in Tools 8000.
2. Click in use.
3. Go to the Serial Interface 1 section in the Serial Interface dialog.
4. Select RS 232 from the Type of Interface list.
5. Select WINMANG from the Device in use list.
6. Enter the CLSS Gateway mainboard name in the Label field.
7. Click OK.
C.4.3 To Use an RS-485 Connection
Using an RS-485 cable the CGW-MB and the panel are connected.
The RS-485 ports in the CLSS Gateway mainboard board are labeled as 3 and 4 in the
Figure
C.2.
1. On the CLSS Gateway mainboard Side
Connect to an RS-485 port of the CLSS Gateway mainboard board.
2. On the Panel Side

• FlexES Panels

• IQ8 Panels
FlexES Panels
• Connect the +ve wire to the Terminal 1 of the panel.
• Connect the -ve wire to the Terminal 2 of the panel.
CGW-MB Installation and Users' Manual | P/N:LS10248-000HW-E | REV.G | JUL/31/2022
Connecting to the Panels
142