  • Page 2: Safety Information

    ・ Do not change the wiring or remove/insert the connectors while the power is turned Failure to observe this caution may result in injury. The PROFIBUS-DP Communication Interface Card SI-P1 is an option card that can be mounted on the inverter control circuit board and used for communications with the PROFIBUS-DP master.
  • Page 3: Profibus-Dp

         : Before Use (1) Read this instruction manual and the instruction manual of the inverter on which the PROFIBUS- DP Communications Interface Card SI-P1 is to be mounted before using the PROFIBUS-DP Communications Interface Card SI-P1 (2) Connect the PROFIBUS-DP communications interface card SI-P1 to the connectors or external terminals where the inverter power supply is turned OFF and the inverter CHARGE indicator lamp is extinguished.
  • Page 4 Confirm that the CHARGE indicator lamp is extinguished. (2) Fit the SI-P1 card connector JP1 to the connector 2CN (number of pins: 60P) on the inverter control board. At this time, insert the two SI-P1 card spacer mounting holes into the option card spacer on the control board until a click is heard, and mount the SI-P1 card firmly.
  • Page 5 Terminal E (For F7 Series) (For F7 Series) Fig. 2 Installation of PROFIBUS-DP Communications Interface Card SI-P1 -  - AUDIN - 7 bis rue de Tinqueux - 51100 Reims - France Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : info@audin.fr...
  • Page 6 Fig. 3 Interconnection Diagram       : Precaution on Wiring NOTE (1) Separate the SI-P1 card communications wiring from main circuit wiring and other power cables. (2) Use a shielded twisted-pair cable conforming to the PROFIBUS specifications for the communications cable.
  • Page 7 − 28-16 2) Refer to Fig. 4 for an illustration of how the end of the connecting cable on the SI-P1 card's side should be prepared. 3) Use a thin screwdriver, less than 2.5mm wide and less than 0.4mm thick, to loosen the terminal screw.
  • Page 8 5.1.1 Address Switches Rotary address switches to set the slave address on the PROFIBUS-DP are provided. Setting address switches 1 and 2 on the SI-P1 card can be used to set the inverter address on the PROFIBUS- Address setting: Address = (setting of address switch 2) × 10 + (setting of address switch 1) × 1 Example)For address "15"...
  • Page 9: Inverter Setting

    5.2 Inverter Setting Execute the following constant setting, whenever necessary, before starting communications between the inverter and the PROFIBUS-DP master. 5.2.1 F7, G7 Series Factory Constant Name Description setting b1-01 Reference selection ∗1 Set the frequency reference input method. 0: Digital Operator 1: Control circuit terminal (analog input) 2: MEMOBUS communications 3: Option Card...
  • Page 10 5.2.2 G5 Series Name Constant Factory Description Setting Operator Display 0: Digital Operator ∗ Reference selection 1: Control circuit terminals (analog inputs) b1-01 2: MEMOBUS communications (using SI-K2) 3: Option Card Reference Source 4: MEMOBUS communications (for CP-717) 0: Digital Operator Operation method selection ∗1 1: Control circuit terminals (sequence inputs) b1-02...
  • Page 11 To configure the SI-P1 card for the PROFIBUS-DP master, the GSD file is necessary. To use the SI-P1 card, register the GSD file in the PROFIBUS-DP master as slave. The GSD file name (YASK00CA.gsd) for the SI-P1 card is the same as the GSD file name for the SI-P card, however the GSD file version is different.