3.3 Use: Status and Alarm Indications

o status indications
!
low priority alarms
!! high priority alarms
SITUATION

Charger on

Mains on.
O
(3.3.1)
UPS output off
Normal
Mains on.
O
operation
UPS output on
(3.3.2)

On battery

Mains off or abnormal, UPS
!
(3.3.3)
output on
UPS on battery, battery

Battery low

!!
(3.3.4)
under drained condition
Mains on, UPS output on.
Replace
!
UPS has failed to pass the
battery (3.3.5)
previous self test
Overload on
Mains on, output power >
!!
105% of the rated capacity.
mains (3.3.6)
Mains off or abnormal,
Overload on
!!
Output power > 105% of the
battery (3.3.6)
rated capacity.
Mains on, unit switches to

Self test

O
battery mode for 6 secs to
(3.3.7)
check the bat. condition
Operating modes and corresponding indications, see 3.3.1 – 3.3.7.
* Reset Buzzer alarm: Press keypad 'ON' for 2 seconds.
Only the actual buzzer is muted; a next alarm re-activates the buzzer.
A buzzer reset does not affect the computer interface alarm.
3.3.1
Charger on
Mains on, UPS output off, the batteries are charging.
3.3.2

Normal operation

Mains on, UPS output on, see also 3.2.1.
OPM_MLE_LTE_350_1K0_1GB_V011
the operating mode
abnormal operating situations
situations in which the actual output voltage of the UPS is no longer
guaranteed; immediate action should be taken
LINE
Green blinking
1x /sec
Green on
Green on
(mains mode)
Green blinking
1x /sec
(standby mode)
Green on
Green on
5
GE Digital Energy
BAT
BUZZER
Beeps
Red on
1x /4 sec
Beeps
Red on
1x /sec
Red
Beeps
blinking
1x /30 sec
1x /30 sec
Continuous
Red on
Continuous
Red on
DE ML Series: user manual 1.1 (GB)
ML Series
RESET
BUZZER
Possible*
Not
possible
Not
possible
Not
possible