Single/dual action manual pull station

Advertisement

WIRING
SUPERVISED STYLE 4/6
REFER TO DLC INSTALLATION
INSTRUCTIONS, P/N 315-033090
LINE 1
1
TO NEXT ADDRESSABLE DEVICE
LINE 2
2
LINE 1
FROM INITIATING CONTROL PANEL
LINE 2
OR PREVIOUS ADDRESSABLE DEVICE
3
EARTH GROUND
Figure 3
Wiring Information
INSTALLATION
Surface Mounting
Flush Mounting
SURFACE
MOUNTING
ENCLOSURE
ELECTRICAL RATINGS
Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ
NOTES:
1. Recommended wire sizes:
2. Wire larger than 14 AWG can damage the connector.
3. When using shielded cable without metal raceway or with
4. When using shielded cable with metal raceway, the wiring shields
5. When using metal raceway without shielded cable, connect the
6. Metal raceway should be thoroughly grounded throughout the system.
7 . In supervisory: All HMS manual stations draw 1mA.
8. All HMS manual stations are polarity insensitive devices. Line 1 and
Distribute the manual station boxes throughout the protected area so that they
are unobstructed, readily accessible, and located in the normal exit path. Place the
manual station according to the regulations of the authorities having jurisdiction.
Mount the backplate to a Model SB-5R Backbox as shown in Figure 4.
Mount the backplate to a user supplied single gang switchbox.
Do not overtighten the screws. Overtightening may distort the backplate.
2¾ in.
MODEL
SB-5R
BACKPLATE
NAMEPLATE
LOCKING
SCREW
HOUSING
ENCLOSURE
Figure 4
Mounting The HMS
D
L
C
/
F
S
D -
M
a
. x
C
r u
e r
t n
firealarmresources.com
18 AWG minimum, 14 AWG maximum
nonmetallic raceway, the shields should be terminated at the device
ground terminal. If the device box is already grounded by another
means, such as being mounted to a grounded structure, the wire
shields should be continuous and must be grounded solely at the point
of origin; for example, at the control panel.
shall be continuous and grounded solely at the point of origin. The
device ground terminal shall be connected to the grounded device box.
device ground terminal to the grounded device box.
Line 2 can be either line of the DLC or FS-DLC loop.
4 in.
5½ in.
HOUSING HINGED
3½ in.
TO BACKPLATE
BACKPLATE
FLUSH
MOUNTING
L
C
L
o
o
p
1
m
A
3½ INCH DEEP
SWITCH BOX
(USER SUPPLIED)
3 in.
P/N 315-033200-7