Installation Instructions
Models HMS-S / HMS-D
Single/Dual Action Manual Pull Station
INTRODUCTION
PROGRAMMING
INSTRUCTIONS
OPERATION
P/N 315-033200-2
The SIEMENS Model HMS-S and HMS-D Manual
Stations are addressable devices containing advanced
control panel communication technology. This technol-
ogy, which provides two-direction communication with
the control panel, produces an Intelligent Initiating
Device. The HMS-S is single action; the HMS-D is
double action.
Refer to Figure 1 to locate the opening on the HMS cover that allows access to the
programming holes which are on the HMS printed circuit board.
To connect the HMS to the DPU Programmer/Tester, insert the plug from the DPU
cable provided with the Programmer/Tester into the opening on the HMS as shown
in Figure 2. Because HMS devices are polarity insensi-
tive, the programming plug can be inserted into the
programming holes in either direction.
To prevent potential damage to the DPU DO NOT
connect an HMS to the DPU until at least one wire is
removed from terminals 1 or 2 of the HMS.
Follow the instructions in the DPU Manual
(P/N 315-033260) to program the HMS to the desired
address. Record the device address on the label
located on the HMS front panel. The HMS can now
be installed and wired to the system.
The HMS-S and HMS-D manual stations operate with the FireFinder-XLS Control
Panel via the DLC Device Loop Card.
The HMS-S and HMS-D manual station housings have a pull down lever that locks in
position after releasing a spring loaded switch. (See Figure 4.) To indicate the manual
station is activated, the pull down lever remains down and locked until the station is
physically reset.
The HMS-D has an additional lever labeled PUSH IN which must be operated first.
Both models are reset by opening the hinged housing cover with an Allen key and
then closing and locking the cover.
Figure 1
HMS Cover
PROGRAMMING
LOCATING TAB
Figure 2
Connecting the DPU Plug
Siemens Building Technologies
OPENING TO
PROGRAMMING
POINTS
POINTS
PLUG FROM
DPU
Fire Safety

Advertisement

loading

Summary of Contents for Siemens HMS-S

  • Page 1 The HMS-S and HMS-D manual stations operate with the FireFinder-XLS Control Panel via the DLC Device Loop Card. The HMS-S and HMS-D manual station housings have a pull down lever that locks in position after releasing a spring loaded switch. (See Figure 4.) To indicate the manual station is activated, the pull down lever remains down and locked until the station is physically reset.
  • Page 2 Figure 3 7 . In supervisory: HMS-S and HMS-D draw 1mA. Wiring Information 8. The HMS-S and HMS-D are polarity insensitive devices. Line 1 and Line 2 can be either line of the loop. INSTALLATION Distribute the manual station boxes throughout the protected area so that they are unobstructed, readily accessible, and located in the normal exit path.