Figure 2: Sample router network
Hub
BMTW BCU
IP: 192.168.0.23
Subnet mask: 255.255.255.0
Gateway: 192.168.0.55
Figure 3: Router ports
10Base2 Ethernet port
Ethernet 1 or ARCNET 1
connected to BACnet
Ethernet 0
connected to IP
Connect PC to router
The router is a single-board computer. It has no
keyboard or display. To interface with the router and
configure it, connect the router to a PC that has a
terminal emulation program such as ProComm™ or
HyperTerminal.
Tracer Summit PC Workstation (v11.0)
IP: 192.168.0.20
Subnet mask: 255.255.255.0
Gateway: 192.168.0.55
Router
IP: 192.168.0.22
Network: 192.168.0.0
Network mask: 255.255.255.0
Broadcast: 192.168.0.255
Default gateway: 192.168.0.55
BACnet Ethernet or ARCNET LAN
BMTS BCU
RJ-45 port
Prior to connecting to the router via terminal
emulation, ensure that the PC satisfies these
requirements:
Serial port cabled to the router console port
(Figure 3) with the provided crossover cable
Properties set to: 9600 baud, 8 bits, 1 stop bit, and
no parity
ANSI command and character sets installed
(VT100 compatible)
3