Application data (cont)
TYPICAL ISOLATION
NOTES:
18
23XRV ISOLATION WITH ACCESSORY SOLEPLATE PACKAGE
ACCESSORY SOLEPLATE DETAIL
1. Dimensions in ( ) are in millimeters.
2. Accessory soleplate package includes 4 soleplates, 16 jacking screws and leveling
pads. Requires isolation package.
3. Jacking screws to be removed after grout has set.
4. Thickness of grout will vary, depending on the amount necessary to level chiller. Use
only pre-mixed non-shrinking grout, Ceilcote 748 or Chemrex Embeco 636 Plus
(38.1) to 0-2
Grout, 0-1
1
/
2
5. Service clearance under the chiller is enhanced if leveling pads are not extended
along the entire length of the heat exchangers.
ISOLATION WITH ISOLATION PACKAGE ONLY
NOTE: Isolation package includes 4 elastomeric pads.
VIEW X-X
(57) thick.
1
/
4
STANDARD ISOLATION
ELASTOMERIC PAD
VIEW Y-Y
(STANDARD)
a23-1647