Electrical data
FRAME SIZE
AA
BA
BB
CC
*Maximum limits only. Additional application limits apply that will reduce these ampacities.
ITEM
Controls, Oil Pump And Heater Circuit†
Oil Pump
Oil Sump Heater
Oil Vaporizer Heater Circuit†
Oil Vaporizer Heater
*Factory wired to VFD.
†Minimum circuit ampacity of 15 amps.
10
VFD FRAME SIZES
MAX INPUT CURRENT*
440
520
520
608
AUXILIARY RATINGS*
VOLTAGE
115
115
115
115
115
MAX OUTPUT CURRENT*
442
442
520
608
MAXIMUM
PROTECTIVE DEVICE
SIZE (AMPS)
15
1.48
4.35
15
13
WATTS
—
130
500
—
1500