Page 1
OWNER’S MANUAL MIRACOOL™ GLASS DOOR MERCHANDISER Manufacturer reserves the right to discontinue,or change at any time, specifications or designs without notice and without incurring obligations. Printed in Mexico 2000L Sales Office: P.O. Box 5932 Spartanburg, S.C. 29304-5932 Technical Service: 1-800-558-7627...
Note: Parts shown are for standard units. Quantity of shelves and clips may vary based on factory-supplied options. GENERAL Page These operation, and maintenance of Carrier Miracool™ series glass door merchandiser units, size 2000L. UNIT INSPECTION Examine all packages for damage to packaging material.
LEVEL UNIT To provide adequate condensate drainage and proper door alignment and operation of unit, the unit cabinet must be level. Leveling feet are factory installed. Remove the front grille to gain access to front and back feet. TO GAIN ACCESS TO LEVELING FEET DANGER Before...
INSTALL SHELVES Product shelves and a bag containing shelf support clips are packed inside the unit. Refer to Table 1 to verify quantity of shelves and shelf supporting clips. Bottom shelf must be placed on interior floor and should be inserted into the two retainer clips provided at the rear corners or the unit floor.
2 inside the cooler. CAUTION Improperly installed lamps may cause damage to the lighting circuit. Carrier will not be responsible for equipment of component falilures or other damages or losses that arise as a result of improper lamp installation.
TABLE 2 – UNIT DATA UNIT Voltage (V) Nominal Range Frequency (Hz) Total Amps Refrigerant Type Charge Amount (oz) Design Pressure (psig) High Side Low Side INITIAL START-UP POWER SUPPLY Connect unit to power supply. Check to verify that the compressor, lamp and fans are running. Important: Low line voltage is often the cause of service complaints.
REFRIGERATION SYSTEM SERVICE COMPONENTS Carrier Miracool™ refrigeration consists of a hermetically sealed compressor and finned evaporator and condenser coils. CONDENSER The condenser has wide finned spaces, which allow more air passage with less dirt or dust accumulation. condenser periodic cleaning for maximum efficiency.
EVAPORATOR COMPARTMENT SERVICING DANGER Before servicing unit, disconnect service. Failure to disconnect electrical service could result in electrical shock and cause personal injury or death. After disconnecting the unit from the power supply, remove the grille retaining screw located in the upper-most part of the grille. (See Figure 2) Lift the grille up and away from the unit.
TABLE 3 – REFRIGERATION SYSTEM SERVICE AND ANALYSIS CHART MALFUNCTION 1. Line cord not plugged in. 2. Fuse removed or blown. Compressor will not start 3. Overload protector tripped. 4. Temp control stuck in open position. - no hum - 5.
MAINTENANCE LAMP REPLACEMENT DANGER Before servicing unit, disconnect service. Failure to disconnect electrical service could result in electrical shock and cause personal injury or death. Remove lamp by rotating lamp 90 degrees to align lamp pins with holder slots. Refer to Bi-Pin Fluorescent Lamp Installation / Verification section on page 5.
Page 13
TABLE 4 –METHODS FOR CLEANING STAINLESS STEEL TASK Routine Cleaning Soap, ammonia or detergent and water Stubborn Spots and Stains, Revere Ware, Goddard’s, Caked-on Splatter, and other Twinkle or Cameo stainless Light Discolorations steel cleaner or Soft Scrub cleaner. Household cleansers, such as Old Dutch, Bon Ami, Ajax, Comet.
Page 14
Copyright 2006 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Printed in Mexico 10-06 79BC560010-01_C...