Carrier 19XL Start-Up, Operation And Maintenance Instructions Manual page 71

Hermetic centrifugal liquid chillers 50/60 hz with hcfc-22 and hfc-134a
Table of Contents

Advertisement

Table 9 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages
G. COMPRESSOR JUMPSTART AND REFRIGERANT PROTECTION
PRIMARY MESSAGE
UNAUTHORIZED
OPERATION
POTENTIAL FREEZE-UP
FAILURE TO STOP
LOSS OF
COMMUNCIATION
STARTER CONTACT
FAULT
POTENTIAL FREEZE UP
*[LIMIT] is shown on the LID as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or
alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.
H. NORMAL RUN WITH RESET, TEMPERATURE, OR DEMAND
PRIMARY MESSAGE
RUNNING — RESET ACTIVE
RUNNING — RESET ACTIVE
RUNNING — RESET ACTIVE
RUNNING — TEMP CONTROL
RUNNING — TEMP CONTROL
RUNNING — TEMP CONTROL
RUNNING — DEMAND LIMITED
RUNNING — DEMAND LIMITED
RUNNING — DEMAND LIMITED
RUNNING — DEMAND LIMITED
RUNNING — DEMAND LIMITED
RUNNING — TEMP CONTROL
RUNNING — DEMAND LIMITED
RUNNING — TEMP CONTROL
NOTE: See Legend on page 68.
with Troubleshooting Guides (cont)
SECONDARY MESSAGE
ALARM MESSAGE/PRIMARY CAUSE
UNIT SHOULD BE
CA
STOPPED
running without control authorization.
EVAP PRESS/TEMP
ERT Emergency: Freeze-up
TOO LOW
prevention.
RUN
DISCONNECT POWER
NECT POWER.
Loss of Communication with Starter:
WITH STARTER
Check chiller.
ABNORMAL 1CR OR
1CR
RUN AUX
Check 1CR/1M aux. contacts.
CRT [VALUE] exceeded limit of
COND PRESS/TEMP
[LIMIT]* Emergency: Freeze-up
TOO LOW
prevention.
SECONDARY MESSAGE
4-20MA SIGNAL
REMOTE SENSOR CONTROL
CHW TEMP DIFFERENCE
LEAVING CHILLED WATER
ENTERING CHILLED WATER
TEMPERATURE RAMP LOADING
BY DEMAND RAMP LOADING
BY LOCAL DEMAND SETPOINT
BY 4-20MA SIGNAL
BY CCN SIGNAL
BY LOADSHED/REDLINE
HOT GAS BYPASS
BY LOCAL SIGNAL
ICE BUILD MODE
P Emergency: Compressor
AUX Emergency: DISCON-
AUX Starter Contact Fault:
Reset program active based upon Config table setup.
Default method of temperature control.
ECW control activated on Config table.
Ramp loading in effect. Use Service1 table to modify.
Ramp loading in effect. Use Service1 table to modify.
Demand limit setpoint is
Demand limit is active based on Config table setup.
Hot Gas Bypass is energized. See surge prevention
in the control section.
Active demand limit manually overridden or Status01
table.
Chiller is running under Ice Build temperature control.
71
ADDITIONAL CAUSE/REMEDY
Compressor is running with more than
10% RLA and control is trying to shut it
down. Throw power off to compressor if
unable to stop. Determine cause before
repowering.
Determine cause. If pumping refrigerant
out of chiller, stop operation and go over
pumpout procedures.
Starter and run and start contacts are
energized while control tried to shut
down. Disconnect power to starter.
Check wiring from PSIO to SMM. Check
SMM module troubleshooting procedures.
Starter run and start contacts energized
while chiller was off. Disconnect power.
The condenser pressure transducer is
reading a pressure that could freeze the
water in the condenser tubes. Check for
condenser refrigerant leaks, bad trans-
ducers, or transferred refrigerant. Place
the unit in Pumpdown mode to eliminate
ALARM if vessel is evacuated.
PROBABLE CAUSE/REMEDY
actual demand.