Carrier 19XL Start-Up, Operation And Maintenance Instructions Manual page 21

Hermetic centrifugal liquid chillers 50/60 hz with hcfc-22 and hfc-134a
Table of Contents

Advertisement

NOTES:
1. Only 12 lines of information appear on the LID screen at any given time. Press NEXT or PREVIOUS to highlight a point or to view points
below or above the current screen.
2. The LID may be configured in English or SI units, as required, through the LID configuration screen.
3. Data appearing in the Reference Point Names column is used for CCN operations only.
4. All options associated with ICE BUILD, Lead/Lag, CCN Occupancy Configuration, and Soft Stopping are only available on PSIO Software
Version 9 and higher.
To access this display from the LID default screen:
1. Press
MENU
.
2. Press STATUS (STATUS01 will be highlighted).
3. Press SELECT .
DESCRIPTION
Control Mode
Run Status
Occupied ?
Alarm State
*Chiller Start/Stop
Base Demand Limit
*Active Demand Limit
Compressor Motor Load
Current
Amps
*Target Guide Vane Pos
Actual Guide Vane Pos
Water/Brine: Setpoint
*
Control Point
Entering Chilled Water
Leaving Chilled Water
Entering Condenser Water
Leaving Condenser Water
Evaporator Refrig Temp
Evaporator Pressure
Condenser Refrig Temp
Condenser Pressure
Discharge Temperature
Bearing Temperature
Motor Winding Temp
Oil Sump Temperature
Oil Pressure Transducer
Oil Pressure
Line Voltage: Percent
Actual
*Remote Contacts Input
Total Compressor Starts
Starts in 12 Hours
Compressor Ontime
*Service Ontime
*Compressor Motor kW
NOTE: All values are variables available for read operation to a CCN. Descriptions shown with (*) support write operations for BEST programming
language, data transfer, and overriding.
Table 2 — LID Screens
EXAMPLE 1 — STATUS01 DISPLAY SCREEN
RANGE
Reset, Off, Local, CCN
Timeout, Recycle, Startup,
Ramping, Running, Demand, Override,
Shutdown, Abnormal, Pumpdown
No/Yes
Normal/Alarm
Stop/Start
40-100
40-100
0-999
0-999
0-999
0-100
0-100
10-120 (–12.2-48.9)
10-120 (–12.2-48.9)
–40-245 (–40-118)
–40-245 (–40-118)
–40-245 (–40-118)
–40-245 (–40-118)
–40-245 (–40-118)
–6.7-420 (–46-2896)
–40-245 (–40-118)
–6.7-420 (–46-2896)
–40-245 (–40-118)
–40-245 (–40-118)
–40-245 (–40-118)
–40-245 (–40-118)
–6.7-420 (–46-2896)
–6.7-420 (–46-2896)
0-999
0-9999
Off/On
0-65535
0-8
0-500000.0
0-32767
0-9999
21
REFERENCE POINT NAME
UNITS
%
%
%
%
AMPS
%
%
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
PSI (kPa)
DEG F (DEG C)
PSI (kPa)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
PSI (kPa)
PSID (kPad)
%
VOLTS
HOURS
HOURS
kW
(ALARM HISTORY)
MODE
STATUS
OCC
ALM
CHIL
S
S
DLM
DEM
LIM
CA
L
CA
P
CA
A
GV
TRG
GV
ACT
SP
LCW
STPT
ECW
LCW
ECDW
LCDW
ERT
ERP
CRT
CRP
CMPD
MTRB
MTRW
OILT
OILP
OILPD
V
P
V
A
REMCON
c
starts
STARTS
c
hrs
S
HRS
CKW