3. Registering MODBUS/TCP Server

3.1.3 Registering PLC configuration

Please register as follows by [Configuration]-[PLC Config.] of the PLCS engineering
tool when you register MODBUS/TCP Server.
The following explains each item.
 PLC Type
Select [21-MODBUS/TCP].
 IP Address
Sets IP address of MODBUS/TCP Server.
 Port No.
Don't set here because this is set in MODBUS/TCP Server configuration.
 Setting Reg(Address)
This parameter isn't used.
 Setting Reg(Number of Words)
This parameter isn't used.
12
Table3.2 Registration of PLC configuration
No.
PLC No.
PLC Type
IP Address
Port No.
Setting Reg
Address
Number of Words
Input Reg
Address
Number of Dig Words
Number of Ana Words
Number of SysAlm Words
1
PLC1
21-MODBUS/TCP
172.16.64.64
0
0
DW00000
500
480
Phase(7W)