installing
Place the stove on a noncombustible floor or on a floor
protector that extends a minimum of 6 inches to the front,
(measured from the glass) 6 inches to the sides and 1 inch
to the rear of the hopper. It is also recommended that floor
protection be installed under any horizontal venting and
extending 2 inches beyond the vent measurement. Material
used for floor protection must be a minimum 3/8" of mate-
rial rated at 0.84k per inch. Another method for calculating
floor protection is in R-value. Minimum permitted is 0.45
R. Example: 1" thickness of a material is rated at 0.52 R,
which would meet the requirement.
Place the stove away from combustible walls at least as
far as shown in Figures 3,4 and 5. Note the difference in
side wall clearance with and without side shields.
Note that the clearances shown are minimum for safety
but do not leave much room for access when cleaning or
servicing.
Connect the power cord to a 120 V.A.C. 60Hz grounded
receptacle. (A surge protector is recommended to protect
the circuit board.) Also be sure that the polarity of the outlet
that the stove is plugged into is correct.
Prior to installing the flue pipe, connect a draft meter. (The
draft meter must have a minimum range of 0-.5.) Record
the first reading. Connect flue pipe to stove and be sure
all doors and windows in the home are closed. Record
the second draft reading_______. If the second reading
is more than .05" lower than the first reading, check for
possible restrictions or the need for outside air (see page
9). For more information on the draft test procedure, refer
to Page 21.
Mobile home installation
When installing this unit in a mobile home, several require-
ments must be followed:
1. The unit must be bolted to the floor. This can be done
with 1/4" lag screws through the 2 holes in the base plate.
2. The unit must also be connected to outside air. See page 9.
3. Floor protection and clearances must be followed as
shown.
4. Unit must be grounded to the metal frame of the mobile
home.
cAutiOn: this appliance must be vented to the outside.
wARning
the StRuc tuRAl integ R itY OF the
MAnuFActuRed hOMe FlOOR,wAll, And
ceiling/ROOF MuSt be MAintAined.
wARning
MObile/MAnuFActuRed hOMe StAndARdS
dO nOt AllOw inStAllAtiOn in ROOMS
deSignAted FOR SleePing.
installation
9" or 13"
9" With Side Shields
13" Without Side Shields
Fig. 4
Floor Protection must meet a minimum
2.24k value or lower. (The lower the k
value, the better the protection.)
18"
9" or 13"
Fig. 3
Fig. 5
Fig. 6
6
P61A Pellet Stove