APPENDIX A — WSHP OPEN SCREEN CONFIGURATION (cont)
SCREEN NAME
POINT NAME
Occupied Heating
Occupied Cooling
Unoccupied Heating
Unoccupied Cooling
Effective Heating
Set Point
Effective Cooling
Set Point
Optimal Start

Configuration

Occupied RH
Set Point
Set Points
Unoccupied RH
Set Point
DCV CTRL Start
Set Point
DCV Max CTRL
Set Point
Start Time
End Time
Mon
Configuration
Tue
Schedule
Wed
Thur
Weekly Schedule
Fri
Sat
Sun
Start Month
Configuration
Start Day
Start Time
Schedule
End Month
End Day
Exception
Schedules 1 - 12
End Time
LEGEND
BAS — Building Automation System
DCV — Demand Controlled Ventilation
IAQ
— Indoor Air Quality
OAT — Outdoor Air Temperature
RH
— Relative Humidity
SAT
— Supply Air Temperature
SPT — Space Temperature
TPI
— Third Party Integration
PASSWORD
EDITABLE
LEVEL
X
X
X
X
X
X
User/Admin
Password level
X
access
X
X
X
X
X
X
X
User/Admin
Password level
X
access
X
X
X
X
X
X
X
User/Admin
Password level
access
X
X
X
45
RANGE
DEFAULT
°
°
40 - 90 F
72 F
°
°
55 - 99 F
76 F
°
°
40 - 90 F
55 F
°
°
55 - 99 F
90 F
°
0 - 10 F
°
0 - 10 F
0 - 100%
65%
0 - 100%
90%
0 - 9999 ppm
500 ppm
0 - 9999 ppm
1050 ppm
00:00 - 23:59
06:00
00:00 - 24:00
18:00
No/Yes
Yes
No/Yes
Yes
No/Yes
Yes
No/Yes
Yes
No/Yes
Yes
No/Yes
No
No/Yes
No
0 - 12
0
0 - 31
0
00:00 - 23:59
0:00
0 - 12
0
0 - 31
0
00:00 - 24:00
0:00
NOTES
Defines the Occupied
Heating Set Point
Defines the Occupied
Cooling Set Point
Defines the Unoccupied
Heating Set Point
Defines the Unoccupied
Cooling Set Point
Takes into effect bias (maximum
allowable set point deviation)
Takes into effect bias (maximum
allowable set point deviation)
Uses historical data to calculate
ramp up time so as to be at set point
at occupied/unoccupied time
Defines the control set point used
during occupied periods (Viewable
only if Humidity Sensor = Installed/
Determines when to start
Dehumidification when occupied)
Defines the control set point used
during unoccupied periods
(Viewable only if Humidity Sensor =
Installed/Determines when to start
Dehumidification when unoccupied)
Defines the control set point used to
start increasing ventilation during
occupied periods (Viewable only if
Ventilation DMP Type = DCV)
Defines the control set point
used to define where the ventilation
will reach its maximum limit during
occupied periods (Viewable only if
Ventilation DMP Type = DCV/Used
to determine DCV ending control
point)
Defines the start time for an
occupied period
Defines the ending time of an
occupied period
Determines if this day is included
in this schedule
Determines if this day is included
in this schedule
Determines if this day is included
in this schedule
Determines if this day is included
in this schedule
Determines if this day is included
in this schedule
Determines if this day is included
in this schedule
Determines if this day is included
in this schedule
Defines the start month of this
hoilday schedule
Defines the start day of this holiday
schedule
Determines the start time for this
schedule
Defines the month to end this
hoilday schedule
Defines the day to end this holiday
schedule
Determines the time to end this
schedule