Replacing The Wshp Open Controller's; Battery; Troubleshooting; Thermistor - Carrier AQUAZONE PCV015-060 Installation And Service Instructions Manual

Compact high-efficiency water source heat pumps with puron refrigerant (r-410a)
Table of Contents

Advertisement

1. Shut off unit main power supply.
2. Loosen bolts on mounting bracket so that fan belt can be
removed.
3. Loosen and remove the 2 motor mounting bracket bolts
on left side of bracket.
4. Slide motor/bracket assembly to extreme right and lift out
through space between fan scroll and side frame. Rest
motor on a high platform such as a step ladder. Do not
allow motor to hang by its power wires.
Replacing the WSHP Open Controller's Bat-
The WSHP Open controller's 10-year lithium
tery —
CR2032 battery provides a minimum of 10,000 hours of data
retention during power outages.
NOTE: Power must be ON to the WSHP Open controller
when replacing the battery, or the date, time and trend data will
be lost.
1. Remove the battery from the controller, making note of
the battery's polarity.
2. Insert the new battery, matching the battery's polarity
with the polarity indicated on the WSHP Open controller.

TROUBLESHOOTING

(Fig. 34 and 35, and Table 29)
When troubleshooting problems with a WSHP, consider the
following.
A thermistor may be required for single-
Thermistor —
phase units where starting the unit is a problem due to low
voltage. See Fig. 34 for thermistor nominal resistance.
The control system employs 2 nom-
Control Sensors —
inal 10,000 ohm thermistors (FP1 and FP2) that are used for
freeze protection. Be sure FP1 is located in the discharge fluid
and FP2 is located in the air discharge. See Fig. 35.
AIRFLOW
(°F)
a50-8163

THERMISTOR

CONDENSATE
LEGEND
COAX — Coaxial Heat Exchanger
Airflow
Refrigerant Liquid Line Flow
AIR
COIL
AIRFLOW
(°F)
EXPANSION
VALVE
FP2
OVERFLOW
LIQUID
(CO)
LINE
AIR COIL
WATER
FREEZE
COIL
PROTECTION
PROTECTION
Fig. 35 — FP1 and FP2 Thermistor Location
WSHP Open Controller —
troller option, the 100 most recent alarms can be viewed using
the BACview
alarm status and alarm history.
6
To view the alarms:
1. Navigate to the Alarm Status screen from the Home
screen using the arrow softkeys. The screen will display
the current alarm status, either normal or Alarm, and al-
low for scrolling through the unit's alarm status.
2. From the Alarm Status screen, press the Alarm softkey to
view the 100 most recent alarms which are labeled with
date and time for easy reference.
NOTE: Active faults can be viewed by scrolling down,
these faults indicate a possible bad sensor or some condi-
tion which may not merit an alarm.
3. To view alarms which have been corrected, scroll down
through the Alarm screen to Return Top Normal screen.
NOTE: Alarms are automatically reset once alarm con-
dition has been corrected.
See Table 29 for possible alarm cause and solution.
90.0
80.0
70.0
60.0
50.0
40.0
30.0
20.0
10.0
0.0
0.0
20.0
Fig. 34 — Thermistor Nominal Resistance
COAX
FP1
WATER IN
WATER OUT
40
With the WSHP Open con-
40.0
60.0
80.0
100.0
120.0
Temperature (degF)
SUCTION
COMPRESSOR
DISCHARGE
140.0