Step 3 - Locate Unit - Carrier AQUAZONE 50PSH Installation And Service Instructions Manual

Single-stage water source heat pumps with puron refrigerant (r-410a)
Table of Contents

Advertisement

Supply Air
Return
Air
Power
Thermostat
Wiring
Compressor
Access Panel
A50-7730
NOTE: Ball valve with integral pressure temperature plug recommended.
Fig. 5 — Typical Vertical Installation — 50PSV Unit
Flexible
Connection
Return
Air
Power
Thermostat
Wiring
Compressor
Access Panel
Supply Air
A50-7729
NOTE: Ball valve with integral pressure temperature plug recommended.
Fig. 6 — Typical Downflow Installation —
50PSD Unit
Step 3 — Locate Unit
should be considered when choosing a location for a WSHP:
• Units are for indoor use only.
• Locate in areas where ambient temperatures are between
39 F and 102 F and relative humidity is no greater than
75%.
• Provide sufficient space for water, electrical and duct
connections.
• Locate unit in an area that allows easy access and removal
of filter and access panels.
• Allow enough space for service personnel to perform
maintenance.
• Return air must be able to freely enter the space if unit needs
to be installed in a confined area such as a closet.
NOTE: Correct placement of the horizontal unit can play an
important part in minimizing sound problems. Since
ductwork is normally applied to these units, the unit can be
placed so that the principal sound emission is outside the oc-
cupied space in sound-critical applications. A fire damper
may be required by the local code if a fire wall is penetrated.
Building
Loop
Flexible
Connection
Water
Out
Water
In
Balancing Valve
Stainless steel
(field-installed
braid hose
accessory)
with integral
"J" swivel
(field-installed
Low Pressure
accessory)
Drop Water
Control Valve
(optional)
(field-installed
accessory)
Ball Valve with optional
integral P/T plug
(typical for supply and
return piping) (field-Installed
accessory)
Building
Loop
Water
Water
Out
In
Stainless
steel
braid hose
with
Balancing Valve
(field-installed
integral "J"
accessory)
swivel(field-
installed
Low Pressure
accessory)
Drop Water
Control Valve
(optional)
(field-installed
accessory)
Ball Valve with
optional integral
Flexible
P/T plug (typical for
Connection
supply and return
piping)(field-installed
accessory)
— The
following
guidelines
FIELD CONVERSION OF DISCHARGE AIR — The dis-
charge air of the 50PSH horizontal units can be converted
between side and back discharge in the field. The conversion
process is the same for right and left return configurations. See
Fig. 7 and 8.
NOTE: It is not possible to convert return air between left or
right return models in the field due to refrigerant piping
changes.
Water
Connection End
Side Discharge
Water
Connection End
Water
Connection End
A50-6256
Back Discharge
Fig. 7 — Conversion Left Return,
Side Discharge to Back Discharge
Return Air
Return Air
Drain
Discharge Air
Fig. 8 — Conversion Right Return,
Side Discharge to Back Discharge
8
Remove Screws
Return Air
Rotate
Return Air
Move to Side
Replace Screws
Return Air
Drain
Discharge Air
Water
Connection End
Supply
Duct
Side Discharge
Water
Connection End
Back Discharge
A50-6257