Single-package rooftop heat pump units
Hide thumbs Also See for 12:
Table of Contents

Advertisement

Table 6 — Fan Performance (SI), 50LJQ008 (50 Hz) — Horizontal Discharge Units
AIRFLOW
50
(L/s)
r/s
BkW
r/s
1100
7.9 0.35
9.4 0.50 10.6 0.68 11.7 0.85 12.7 1.03 13.6 1.25 14.4 1.46 14.9 1.69 15.1 1.92 15.0 2.15
1200
8.3 0.42
9.8 0.59 11.0 0.78 12.0 0.95 13.0 1.15 13.9 1.36 14.8 1.58 15.5 1.82 16.0 2.06 16.4 2.31
1300
8.8 0.51 10.2 0.69 11.3 0.88 12.4 1.08 13.3 1.28 14.2 1.49 15.0 1.72 15.8 1.96 16.5 2.21 17.1 2.47
1400
9.2 0.60 10.6 0.80 11.7 0.99 12.7 1.22 13.7 1.42 14.5 1.63 15.3 1.87 16.1 2.12 16.9 2.38
1500
9.7 0.71 11.0 0.91 12.1 1.12 13.0 1.35 14.0 1.59 14.8 1.81 15.6 2.04 16.4 2.30
1600
10.1 0.82 11.3 1.04 12.5 1.28 13.4 1.49 14.3 1.75 15.2 2.00 15.9 2.24
1700
10.6 0.93 11.8 1.20 12.9 1.44 13.8 1.67 14.7 1.92 15.5 2.20
Table 7 — Fan Performance (SI), 50LJQ012 (50 Hz) — Horizontal Discharge Units
AIRFLOW
50
(L/s)
r/s
BkW
r/s
1300
7.6 0.30
8.9 0.41 10.2 0.56 11.1 0.64 12.1 0.77 13.1 0.92 13.9 0.93 14.0 0.52 15.0 1.13 15.6 1.32
1400
8.0 0.40
9.3 0.51 10.5 0.64 11.4 0.75 12.4 0.88 13.3 1.01 14.1 1.11 14.6 0.96 15.4 1.32 16.0 1.42
1500
8.4 0.48
9.6 0.60 10.7 0.72 11.8 0.86 12.7 0.99 13.5 1.12 14.3 1.26 15.1 1.35 15.7 1.49 16.4 1.54
1600
8.8 0.58 10.0 0.69 11.1 0.82 12.1 0.96 12.9 1.10 13.8 1.24 14.5 1.38 15.3 1.54 16.0 1.64 16.7 1.72
1700
9.1 0.69 10.3 0.78 11.3 0.93 12.3 1.07 13.2 1.22 14.0 1.37 14.8 1.52 15.5 1.66 16.3 1.84 17.0 1.95
1800
9.5 0.81 10.7 0.90 11.7 1.05 12.6 1.20 13.5 1.36 14.3 1.52 15.0 1.67 15.8 1.83 16.4 1.99 17.2 2.17
1900
9.9 0.95 11.0 1.02 12.0 1.18 12.9 1.34 13.8 1.50 14.6 1.68 15.3 1.83 16.0 2.00 16.7 2.16 17.3 2.33
2000
10.3 1.11
11.4 1.17 12.3 1.32 13.2 1.48 14.1 1.66 14.9 1.83 15.6 2.01 16.3 2.18 17.0 2.36 17.6 2.53
2100
10.7 1.29 11.8 1.33 12.7 1.47 13.5 1.65 14.4 1.84 15.1 2.00 15.9 2.20 16.6 2.38
2200
11.2 1.48 12.1 1.51 13.1 1.64 13.9 1.83 14.6 2.01 15.4 2.20 16.2 2.38
2300
11.6 1.70 12.5 1.71 13.4 1.83 14.2 2.01 15.0 2.20 15.7 2.41
Table 8 — Fan Performance (SI), 50LJQ008 (50 Hz) — Vertical Discharge Units
AIRFLOW
50
(L/s)
r/s
BkW
r/s
1100
8.7 0.42 10.1 0.59 11.1 0.75 12.2 0.93 13.1 1.12 14.0 1.30 14.8 1.51 15.7 1.77 16.4 2.02 17.2 2.35
1200
9.3 0.52 10.5 0.69 11.6 0.87 12.6 1.05 13.5 1.26 14.3 1.46 15.1 1.66 15.9 1.88 16.7 2.14 17.4 2.44
1300
9.8 0.64 11.0 0.81 12.1 1.01 13.0 1.20 13.9 1.41 14.7 1.63 15.5 1.84 16.2 1.98 16.9 2.29 17.6 2.56
1400
10.4 0.77 11.5 0.94 12.6 1.16 13.5 1.37 14.3 1.58 15.1 1.80 15.9 2.04 16.6 2.27 17.3 2.51
1500
11.0 0.92 12.0 1.10 13.0 1.33 13.9 1.56 14.7 1.78 15.5 2.00 16.3 2.25 17.0 2.50
1600
11.6 1.08 12.6 1.28 13.5 1.50 14.4 1.76 15.2 2.00 16.0 2.23 16.7 2.47
1700
12.2 1.26 13.1 1.48 14.0 1.70 14.9 1.97 15.7 2.23 16.4 2.48
Table 9 — Fan Performance (SI), 50LJQ012 (50 Hz) — Vertical Discharge Units
AIRFLOW
50
(L/s)
r/s
BkW
r/s
1300
8.4 0.37
9.6 0.51 10.8 0.61 11.7 0.69 12.6 0.81 13.3 0.90 14.3 1.05 15.1 1.27 15.9 1.48 16.7 1.67
1400
8.8 0.46 10.0 0.59 11.1 0.71 12.0 0.82 12.9 0.93 13.7 1.04 14.5 1.17 15.4 1.35 16.2 1.56 16.8 1.75
1500
9.2 0.55 10.4 0.68 11.5 0.81 12.4 0.94 13.2 1.06 14.0 1.19 14.8 1.26 15.6 1.44 16.4 1.62 17.1 1.83
1600
9.7 0.65 10.8 0.79 11.8 0.93 12.8 1.07 13.6 1.19 14.4 1.33 15.1 1.46 15.8 1.59 16.5 1.72 17.3 1.91
1700
10.2 0.75 11.2 0.91 12.2 1.06 13.1 1.20 13.9 1.34 14.7 1.48 15.4 1.63 16.1 1.76 16.7 1.89 17.4 2.04
1800
10.6 0.87 11.7 1.05 12.6 1.20 13.5 1.35 14.3 1.51 15.0 1.65 15.7 1.80 16.4 1.95 17.1 2.10 17.7 2.24
1900
11.1 1.01 12.1 1.19 13.0 1.35 13.9 1.52 14.7 1.68 15.4 1.84 16.1 1.99 16.8 2.14 17.4 2.31 18.0 2.46
2000
11.6 1.16 12.5 1.35 13.4 1.52 14.3 1.69 15.0 1.86 15.8 2.04 16.5 2.21 17.1 2.36 17.7 2.53
2100
12.0 1.32 13.0 1.53 13.8 1.70 14.6 1.88 15.4 2.07 16.1 2.25 16.8 2.43
2200
12.5 1.50 13.4 1.71 14.3 1.91 15.1 2.09 15.8 2.29 16.5 2.48
2300
13.0 1.70 13.9 1.91 14.7 2.13 15.5 2.31 16.2 2.52
LEGEND
r/s
— Wheel Speed (Revolutions per Second)
Bkw — Fan Shaft Power (kW)
NOTES:
1. Boldface indicates field-supplied drive required.
2.
indicates field-supplied motor and drive required.
3. Maximum usable output power (BkW) on the 50LJQ008 unit is 1.79
(2.40 Bhp) with standard 1.12 BkW (1.5 hp) motor. The maximum
usable output power (BkW) increases to 2.16 (2.90 Bhp) on the
50LJQ012 unit with standard 1.5 BkW (2 hp) motor. Extensive
EXTERNAL STATIC PRESSURE (Pa)
100
150
200
BkW
r/s
BkW
r/s
BkW
EXTERNAL STATIC PRESSURE (Pa)
100
150
200
BkW
r/s
BkW
r/s
BkW
EXTERNAL STATIC PRESSURE (Pa)
100
150
200
BkW
r/s
BkW
r/s
BkW
EXTERNAL STATIC PRESSURE (Pa)
100
150
200
BkW
r/s
BkW
r/s
BkW
250
300
350
r/s
BkW
r/s
BkW
r/s
250
300
350
r/s
BkW
r/s
BkW
r/s
250
300
350
r/s
BkW
r/s
BkW
r/s
250
300
350
r/s
BkW
r/s
BkW
r/s
motor and electrical testing on the Weathermaker I units ensures
that the full power range of the motor can be utilized with confi-
dence. Using the fan motors up to the power ratings shown will
not result in nuisance tripping or premature motor failure. Unit war-
ranty will not be affected.
4. Use of field-supplied motor may affect wire sizing. Contact
Carrier representative to verify.
5. Values include losses for filters, unit casings and wet coils.
6. Motor drive range is 10.30 to 14.70 r/s (622 to 882 rpm) on the
50LJQ008 and 11.50 to 15.00 r/s (692 to 896 rpm) on the 50LJQ012.
All other r/s (rpms) will require a field-supplied drive.
15
400
450
BkW
r/s
BkW
r/s
BkW
400
450
BkW
r/s
BkW
r/s
BkW
400
450
BkW
r/s
BkW
r/s
BkW
400
450
BkW
r/s
BkW
r/s
BkW
500
r/s
BkW
500
r/s
BkW
500
r/s
BkW
500
r/s
BkW