Specifications; Regulatory Information; Contact Information - GE 250-CO Installation Sheet

Carbon monoxide detector

Advertisement

General limitations of CO detectors
CO detectors require a source of power to work. Verify that the
green LED on the detector is flashing at all times. Since this unit is
powered by a control panel, it may not operate during a power
failure or if the control panel is disabled.
WARNING:
This product is intended for use in ordinary indoor
locations of family living units. It is not designed to meet
compliance with Occupational Safety and Health Administration
(OSHA) commercial or industrial standards.
The 250-CO detector is not intended to meet the requirements of
CAN/CSA-6.19 (Residential Carbon Monoxide Alarming Devices).
Please check with the local codes concerning the applicability of
this requirement for each installation.
People with special medical problems should consider using
specialized detection devices with less than 30 ppm (parts per
million) alarming capabilities.
This detector only indicates the presence of carbon monoxide gas
at the detector. CO may be present in other areas. Anything
preventing CO from reaching the detector, such as closed doors,
could delay or prevent detector activation.
If the unit is in trouble or at the end of its life, it may not sense CO
and cannot be relied upon to monitor carbon monoxide levels.
CO detectors are not smoke detectors:
to detect CO from any combustion source. It is not designed to
detect smoke, fire, or any other gas.
CO detectors may not be heard:
who has taken drugs or alcohol, may not awaken if the detector is
installed outside a bedroom. Normal noise due to stereos,
television, etc. may also prevent the detector from being heard if
distance or closed or partly closed doors muffle the sounder. This
unit is not designed for the hearing impaired.
CO detectors are not a substitute for life insurance:
these detectors will warn against increasing CO levels, we do not
warrant or imply in any way that they will protect lives from CO
poisoning. They should only be considered as an integral part of a
comprehensive safety program.
P/N 1061018 • REV D • ISS 10FEB10
This detector is designed
A sound sleeper, or someone
Though

Specifications

Input voltage
12 or 24 VDC supplied by control panel or
resettable auxiliary power supply
Current consumption
Normal
20 mA
Alarm
40 mA (75 mA in test)
Alarm relay
150 mA at 33 VDC
Type
Form C
UL rating
Zone
Common trouble relay
150 mA at 33 VDC
Type
Normally opened held closed with power
applied
UL rating
Common
CO alarm level
70 ppm/60 to 240 minutes
Sounder
85 dB
Compatible control panel
UL 985 or UL 864 Listed
Compatible electrical box
North American 2-1/2 in. (64 mm) deep single-
gang
Wire size
14 to 22 AWG (0.25 to 2.0 mm²)
Dimensions (W x L x D)
Detector
3.1 x 4.6 x 1.3 in. (7.8 x 11.7 x 3.2 cm)
Adapter plate
4.5 x 6.5 x 0.2 in. (11.4 x 16.5 x 0.5 cm)
Weight
Detector
4.7 oz. (133 g)
Adapter plate
1.6 oz (46 g)
Color
White
Operating environment
Temperature
32 to 104°F (0 to 40°C)
Relative humidity
0 to 90%, noncondensing
Altitude
Less than 6,000 ft. above sea level

Regulatory information

Manufacturer
GE Security, Inc.
HQ and regulatory responsibility:
GE Security, Inc., 8985 Town Center Parkway,
Bradenton, FL 34202, USA
Year of
The first two digits of the product serial number
manufacture
(located on the product identification label) are the
year of manufacture.
UL rating
12 VDC, 24 VDC
North American
UL 2075
This detector has been evaluated to the CO alarm
standards
sensitivity limits of UL 2034.

Contact information

For contact information see our Web site: www.gesecurity.com