Storage Temperature
–40 to 150°F (–40 to 65°C)
Shipping Temperature
–40 to 150°F (–40 to 65°C)
Relative Humidity
5% to 95% RH non-condensing
Economizer Module Wiring Details
Use Fig. 42 and Tables 4 and 5 to locate the wiring ter-
minals for the Economizer module.
NOTE: The four terminal blocks are removable. Slide out each
terminal block, wire it, and then slide it back into place.
MAT
MA
MAT
MA
OAT
OA
OAT
OA
S-BUS
SB
SB
S-BUS
SB
SB
SB
SB
V
IAQ 2-10
C
R
IAQ COM
IAQ 24V
V
C
ACT 2-10
R
NA
ACT COM
ACT 24V
50040839-001
Rev. G
Fig. 42 — W7220 Wiring Terminals
NA
AUX2-
NA
OCC
A2
OC C
E-GND
EXH1
EX
A1
AUX1-O
Cert
Product
California Title 24, Part 6
HJW10
www.energy.ca.gov
Y2-
Y2I
Y2O
Y2-O
Y1I
Y1-
Y1O
Y1-O
C
R
C
R
50048848-002
Rev. A
27
Table 4 — Economizer Module - Left Hand
Terminal Blocks
LABEL
TYPE
Top Left Terminal Block
MAT
20k NTC
Mixed Air Temperature Sensor
MAT
and COM
(Polarity Insensitive Connection)
OAT
20k NTC
Outdoor Air Temperature Sensor
OAT
and COM
(Polarity Insensitive Connection)
S-BUS
S-BUS
Enthalpy Control Sensor
*
S-BUS
(Sylk
Bus)
(Polarity Insensitive Connection)
Bottom Left Terminal Block
Air Quality Sensor Input (e.g. CO
IAQ 2-10
2-10 vdc
sensor)
IAQ COM
COM
Air Quality Sensor Common
IAQ 24V
24 vac
Air Quality Sensor 24 vac Source
ACT 2-10
2-10 vdc
Damper Actuator Output (2-10 vdc)
ACT COM
COM
Damper Actuator Output Common
ACT 24v
24 vac
Damper Actuator 24 vac Source
*Sylk is a trademark of Honeywell International Inc.
Table 5 — Economizer Module - Right Hand
Terminal Blocks
LABEL
TYPE
Top Right Terminal Blocks
AUX2 I
24 vac IN
The first terminal is not used.
Shut Down (SD) or HEAT (W)
Conventional only
OCC
24 vac IN
and
Heat Pump Changeover (O-B) in Heat
Pump mode.
E-GND
E-GND
Occupied/Unoccupied Input
24 vac
EXH1
Exhaust Fan 1 Output
OUT
Programmable:
Exhaust fan 2 output
24 vac
or
AUX1 O
OUT
ERV
or
System alarm output
Bottom Right Terminal Blocks
Y2 in - Cooling Stage 2 Input from
Y2-I
24 vac IN
space thermostat
24 vac
Y2 out - Cooling Stage 2 Output to
Y2-O
OUT
stage 2 mechanical cooling
Y1 in - Cooling Stage 2 Input from
Y1-I
24 vac IN
space thermostat
24 vac
Y1 out - Cooling Stage 2 Output to
Y1-O
OUT
stage 2 mechanical cooling
C
COM
24 vac Common
R
24 vac
24 vac Power (hot)
DESCRIPTION
2
DESCRIPTION