Start-Up; Service - Carrier ROOMTOP 50AH024-096 Installation And Service Instructions Manual

Horizontal indoor single-package cooling units with puron refrigerant (r-410a)
Table of Contents

Advertisement

UNIT
SIZE
CFM
50AH
Rpm
024
1700
247
036
2000
276
048
2500
251
060
3000
287
072
5200
367
096
6400
448
LEGEND
Bhp
— Brake Horsepower

START-UP

Make sure unit has been installed in
Unit Preparation —
accordance with installation instructions and applicable codes.
Compressor Mounting —
mounted on rubber-in-shear (RIS) isolators. Do not loosen or
remove compressor holddown bolts.
Check all electrical connections in
Internal Wiring —
unit control boxes and tighten as required.
Refrigerant Service Valves —
2 Schrader-type service ports, one on the suction line and one
on the compressor discharge line. Be sure that caps on the ports
are tight.
Compressor Rotation —
units, it is important to be certain compressor is rotating in the
proper direction. To determine whether or not compressor is
rotating in the proper direction:
1. Connect service gages to suction and discharge pressure
fittings.
2. Energize the compressor.
3. The suction pressure should drop and the discharge pres-
sure should rise, as is normal on any start-up.
If the suction pressure does not drop and the discharge pres-
sure does not rise to normal levels:
1. Note that the condenser and evaporator fans may also be
rotating in the wrong direction.
2. Turn off power to the unit and tag disconnect.
3. Reverse any two of the unit power leads.
4. Reapply power to the unit; remove tag.
5. Verify correct refrigerant pressures.
The suction and discharge pressure levels should move to
their normal start-up levels.
NOTE: When the compressor is rotating in the wrong direc-
tion, the unit will sound louder than normal and will not
provide cooling.
To start unit, turn on main power supply. Set
Cooling —
system selector switch at COOL position and fan switch at
AUTO. position. Adjust thermostat to a setting below room
temperature. Compressor, condenser and evaporator motors
start on closure of contactors.
TO SHUT OFF UNIT — Set system selector switch at OFF
position or reset thermostat at a position above room
temperature.
Table 4 — Condenser-Fan Performance
0.0
0.1
Bhp
Rpm
Bhp
0.07
255
0.07
0.11
282
0.11
0.17
305
0.18
0.22
334
0.28
0.68
438
0.89
1.26
524
1.59
Compressors are internally
Each unit system has
On 50AH036-096, 3-phase
EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.3
Rpm
Bhp
Rpm
262
0.08
269
289
0.12
295
357
0.22
408
378
0.33
421
464
0.98
490
546
1.70
568
NOTES:
1. Refer to Table 1 for condenser fan motor and drive information.
2. Upgrade 1 Static Motor is required for boldface values.
3. Upgrade 2 Static Motor is required for shaded values.
Disconnect all power to the unit before performing mainte-
nance or service. Electrical shock and personal injury could
result.
IMPORTANT: If repairs to refrigerant cycle compo-
nents (e.g., compressor, filter drier, etc.) are required,
recover all refrigerant from the system by using both
high and low-pressure ports. Then remove base unit
from the space.
Filters are disposable and should be inspected and
Filters —
replaced at regular intervals monthly or as conditions require.
They are located in front of the evaporator coil and may be re-
moved by sliding them horizontally out to edge of unit. See
Fig. 2-5. No tools are required for installation or removal of
filters.
Condenser Coil —
through the side access panel on condenser section, or through
side access panel on condenser section. Use a stiff brush when
cleaning coil. Be careful not to bend aluminum fins.
Evaporator Coil —
cleaning through the side access panel on evaporator section.
When necessary, wash coil with a commercial cleaner (Oakite
164) or dishwasher detergent using a pressurized spray canis-
ter. Flush coil from return-air duct side and take care not to get
water in ductwork or unit insulation.
Condensate Drain —
least once a year to prevent sludge build-up.
Lubrication —
tor motors is not necessary since both are equipped with
permanently lubricated bearings. Do not oil.
Unit Condenser Motor —
belt-driven adjustable-pulley fan systems. The unit fan motors
are shipped with adjustable pulley at 4 turns open.
Blower Wheel Servicing —
ommended for the evaporator and condenser blowers. Both are
removed by loosening and removing the 2 screws (sizes 024-
060) or 4 screws (sizes 072 and 096) that hold them in place. In
both cases, the entire assembly is then moved outside of the
base unit. Once outside, the blower wheel and condenser shaft
bearings and/or evaporator motor can be serviced.
17
0.4
Bhp
Rpm
Bhp
Rpm
0.08
277
0.08
0.12
301
0.12
0.27
456
0.32
0.38
464
0.43
1.07
516
1.16
1.81

SERVICE

WARNING
The condenser coil is accessible
The evaporator coil is accessible for
Clean and empty drain pan at
Lubrication of the condenser and evapora-
All 50AH units contain
In-space servicing is rec-
0.5
Bhp
284
0.09
307
0.13
501
0.37
505
0.49
542
1.25

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents