CONTENTS
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-17
Step 5 - Make Condensate Piping
Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Step 7 - Split Systems (Factory Option,
if Required). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
• FIELD CONTROL WIRING
• THERMOSTAT WIRE
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17,18
SAFETY CONSIDERATIONS
Installing and servicing air-conditioning equipment can be
hazardous due to system pressure and electrical components.
Only trained and qualified service personnel should install,
repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func-
tions such as cleaning coils and filters and replacing filters. All
other operations should be performed by trained service per-
sonnel. When working on air-conditioning equipment, observe
precautions in the literature and on tags and labels attached to
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations. Have
fire extinguisher available.
WARNING
Disconnect all power to the unit before performing mainte-
nance or service. Electrical shock and personal injury could
NOTE: Ensure voltage on unit agrees with voltage listed on
the unit rating plate.
GENERAL
The 50AH024-096 units are single-package, indoor, hori-
zontally mounted air conditioners of 2 to 8 tons capacity. The
50AH units are ASHRAE (American Society of Heating, Re-
frigerating and Air Conditioning Engineers) 90.1 compliant.
These units can be mounted as factory-shipped single-
package units or can be separated and mounted as a split
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53500057-01
Horizontal Indoor Single-Package Cooling Units
Installation, Start-Up, and
Service Instructions
Printed in U.S.A.
with PURON
system. If unit is split, the condensing section must be mounted
horizontally.
All units are designed to be ducted on both the condenser
and evaporator sides. Centrifugal blowers are used to ensure
quiet air delivery to the conditioned space. Sound level
requirements should be determined before final unit installa-
tion site is chosen.
Unit servicing is relatively simple since access to the con-
denser and evaporator motors, blowers, belt, and pulley is
gained through access panels located on the sides of the unit.
These panels may also be used for cleaning of condenser coils.
Unit side panels also provide access to control box and pres-
sure switches.
Refrigeration cycle components (e.g., compressor, filter
drier, etc.) can be serviced upon removal of the base unit from
the space.
Determine building alterations required to run piping, wir-
ing, and ductwork. Follow dimensional drawings carefully
for ductwork, piping locations, electrical wiring, and over-
all unit dimensions. Read all installation instructions before
starting installation.
The 50AH units are intended for indoor installation only.
Step 1 - Receive and Inspect Unit -
check unit against shipping order. See Fig. 1 for model number
nomenclature. Inspect carefully for concealed shipping dam-
age. If unit is damaged or incomplete, file claim with transpor-
tation company and advise Carrier immediately.
Step 2 - Protect Unit from Damage -
tain warranty, unit must be protected against theft and vandal-
ism and stored indoors at all times.
Step 3 - Provide Unit Support -
for unit dimensions. Refer to Table 1 for unit sizes and weights.
Each unit requires the following field-supplied items:
8 - threaded suspension rods (
minimum), 4 additional rods are needed if the unit
has a factory-installed air-side economizer
8 - washers
8 - locknuts
Install the 8 field-supplied rods by suspending them from a
suitable ceiling support. Locate rods to mate with 8 outside cor-
ner rigging holes shown in Fig. 2-5. Unit center of gravity is
shown in Fig. 6.
The ceiling and ceiling supports of existing buildings may
require reinforcements; follow all applicable codes.
Form 50AH-14SI
Pg 1
ROOMTOP
50AH024-096
®
Refrigerant (R-410A)
INSTALLATION
WARNING
Refer to Fig. 2-5
3
/
-in.-16 SAE Grade 1
8
5-10
Replaces: 50AH-12SI
®
Unpack and
To main-