Chapter 5: Card Bring-Up And Validation; Environment Setup - Xilinx Alveo U50 Installation Manual

Data center accelerator card
Hide thumbs Also See for Alveo U50:
Table of Contents

Advertisement

Card Bring-Up and Validation
After installing the XRT and deployment platform, the card installation can be verified using the
following commands, which are explained in more detail below.
• lspci
• xbmgmt examine
• xbutil validate
The lspci Linux command is used to confirm the card is seen by the OS.
The additional commands are used to validate and identify the installed card(s) and report
additional card details including memory, PCIe
xbutil
and
xbmgmt
Note: Utility command line help can always be obtained using the --help option.
Related Information
Installing the Card

Environment Setup

Set the environment to use the utilities by running the following command. Note that the
command is dependent on the command shell you are using.
Use the following command in csh shell:
$ source /opt/xilinx/xrt/setup.csh
Use the following command in bash shell:
$ source /opt/xilinx/xrt/setup.sh
UG1370 (v1.8) October 28, 2021
Alveo U50 Data Center Accelerator Card Installation Guide

Chapter 5: Card Bring-Up and Validation

®
, platform name, and system information. See
Send Feedback
Chapter 5
www.xilinx.com
21