Routing Power Leads Into Unit; Connecting Ground Lead To Ground Screw; Routing Control Power Wires; Accessory Installation - Carrier Infinity 48XL Installation Instructions Manual

15 seer single packaged air condotioner and gas furnace system with puron (r-410a) refrigerant
Hide thumbs Also See for Infinity 48XL:
Table of Contents

Advertisement

Table 2 - Maximum
G as Flow Capacity*
NOMINAL
INTERNAL
LENGTH OF PIPE ft (m)'{"
IRON PIPE
DIAMETER
10
20
30
40
50
60
70
80
90
100
125
150
175
200
SIZE
(IN.)
(IN.)
(3.0)
(6.1)
(9.1)
(12.1)
(15.2)
(18.3)
(21.3)
(24.4)
(27.4)
(30.5)
(38.1)
(45.7)
(53.3)
(61.0)
1/2
.622
175
120
97
82
73
66
61
57
53
50
44
40
--
--
3/4
.824
360
250
200
170
151
138
125
118
110
103
93
84
77
72
1
1.049
680
465
375
320
285
260
240
220
205
195
175
160
145
135
1 - 1/4
1.380
1400
950
770
600
580
530
490
460
430
400
360
325
300
280
1 - 1/2
1.610
2100
1460
1180
990
900
810
750
690
650
620
550
500
460
430
*Capacity
of pipe in cu ft of gas per hr for gas pressure of 0.5 psig or less. Pressure drop of 0.5-IN.
W.C. (based on a 0.60 specific gravity gas). Refer to Table,
NFPA 54/ANSI Z223,1.
1- This length includes an ordinary
number
of fittings.
ROUTING
POWER
LEADS
INTO UNIT
Use only
copper
wire
between
disconnect
and unit.
The
high
voltage
leads should be in a conduit
until they enter the duct panel;
conduit
termination
at the duct panel
must be watertight.
Run the
high-voltage
leads
through
the
power
entry
knockout
on the
power
entry side panel.
See Fig. 5 and 6 for location
and size. For
single-phase
units, connect
leads to the black and yellow wires.
CONNECTING
GROUND
LEAD
TO GROUND
SCREW
Connect
the ground
lead to the chassis
using the ground
screw on
the control
plate near the inducer
switch (See Fig. 13).
ROUTING
CONTROL
POWER
WIRES
For detailed
instruction
on the low voltage
connections
to the User
Interface
(UI), refer to the UI installation
guide.
Form
a drip-loop
with the control
leads before routing
them into
the unit.
Route the low voltage
control
leads
through
grommeted,
low-voltage
hole provided
into unit (See Fig. 5 and 6). Connect
user interface
leads to unit control power
leads as shown in Fig. 14.
The unit transformer
supplies
24-v
power
for complete
system
including
accessory
electrical
heater. Transformer
is factory
wired
for 230-v
operation.
If supply voltage
is 208-v,
rewire transformer
primary
as described
in Special
Procedures
for 208-v
Operation
section.
The furnace
board
is fused by a board-mounted
automotive
fuse
placed in series with transformer
SEC1 and R circuit. The C circuit
of transformer
circuit
is referenced
to chassis
ground
through
a
printed circuit run at SEC2
and gas valve grounding
wire. Check to
be
sure
control
board
is
mounted
securely
using
both
factory-installed
screws.
ACCESSORY
INSTALLATION
A. Outdoor
Air Thermistor
(OAT)
EQUIPMENT
OPERATION
HAZARD
The installation
of an outdoor
temperature
sensor
using the
Infinity
control
board
OAT
terminals
is required.
Many
Infinity
features
(auto
humidity
control,
comfort
rollback,
ETC.) will be lost if the OAT is not connected.
For
detailed
mounting
instructions
for the
OAT
sensor,
please
refer to TSTATXXSEN01-B
installation
instructions
(catalog
no. 63TS-TAI3):
Procedures
1 through
3.
The
OAT input
is used
to supply
outdoor
temperature
data for
system
level
functions
and
for
temperature
display
on
User
Interface
(UI). Using
two wires
of the field-supplied
thermostat
wire cable, wire the ends of the two black
OAT pigtails.
Wire the
opposite
ends of these two wires to the OAT provided
with the UI.
There
is no polarity
to be observed.
NOTE:
Mis-wiring
OAT inputs will not cause
damage
to either
Infinity
control
or thermistor.
If the thermistor
is wired incorrectly,
no reading
will
appear
at UI.
Re-wire
thermistor
correctly
for
normal
operation.
B.
Humidifier
Connections
The furnace
control
board
terminal
marked
HUM
is provided
for
low
voltage
(24-vac)
control
of a humidifier.
No
humidistat
is
required
as UI monitors
indoor
humidity.
When
commanded
to operate
humidifier,
the unit
control
will
energize
the HUM
output
to turn humidifier
on and de-energize
HUM
output
to
turn
humidifier
off.
Wire
HUM
and
COM
terminals
directly
to humidifier
as shown
in Fig. 14.
C.
Electronic
Air Cleaner
Electronic
Air
Cleaner
terminals
are provided
on the
Infinity
Control
Board (EAC-I
and EAC-2).
While these terminals
can be
used to power
a 230V
EAC, it is recommended
that any EAC be
installed
per
the
EAC
installation
instructions
and
connected
separately
to a standard
II5V
or 230V
outlet
with
an airflow
sensor to control operation
of the EAC.
SPECIAL
PROCEDURES
FOR 208-V
OPERATION
Be sure unit disconnect
switch
is open.
Disconnect
the black primary
lead
from the transformer.
See unit
wiring
label (See Fig. 16 and 17).
Connect
the black primary
lead to the transformer
terminal
labeled
208-v.
12

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents