Check For Refrigerant Leaks; Start-Up Adjustments; Checking Cooling And Heating Control Operation; Checking And Adjusting Refrigerant Charge - Carrier Infinity 48XL Installation Instructions Manual

15 seer single packaged air condotioner and gas furnace system with puron (r-410a) refrigerant
Hide thumbs Also See for Infinity 48XL:
Table of Contents

Advertisement

BURNER
FLAME
BURNER
MANIFOLD
Fig. 21 - Monoport
Burner
C99021
LIMIT
SWITCHES
Normally
closed
limit switch
(LS)
completes
the control
circuit.
Should
the
leaving-air
temperature
rise
above
the
maximum
allowable
temperature,
the
limit
switch
opens
and
the
control
circuit "breaks."
Any
interruption
in the
control
circuit
instantly
closes the gas valve
and stops gas flow to the burners
and pilot.
The blower
motor
continues
to run until
LS resets. The furnace
board STATUS
LED will display
STATUS
CODE
33.
When
the
air
temperature
at the
limit
switch
drops
to the
low-temperature
setting
of the limit switch,
the switch
closes
and
completes
the
control
circuit.
The
direct-spark
ignition
system
cycles and the unit returns
to normal
heating
operation.
ROLLOUT
SWITCH
The function
of the rollout
switch is to close the main gas valve in
the event
of flame rollout.
The switch
is located
above the main
burners.
When
the temperature
at the rollout
switch
reaches
the
maximum
allowable
temperature,
the control
circuit
trips, closing
the gas valve
and stopping
gas flow to the burners.
The indoor
fan
motor
(IFM)
continues
to run until switch
is reset. The furnace
board STATUS
LED will display
STATUS
CODE
33.
CONTINUOUS
FAN MODE
When continuous
fan operation
is requested
by the UI indoor
fan
motor will operate
at continuous
blower
airflow.
Continuous
fan
operation
is programmable.
See
the
UI
Owner's
Manual
for
detailed
instructions.
Terminal
EAC-I
is energized
as long as the
indoor
fan motor is energized.
During
a call for gas heat,
the Infinity
control
will transition
the
indoor
fan motor to continuous
blower
airflow
or gas heat airflow,
whichever
is lowest.
The indoor
fan motor will remain
ON until
the
burners
ignite,
then
shut
OFF
and
remain
OFF
for
the
blower-ON
delay
allowing
the heat exchangers
to heat up more
quickly,
then restarts
at the end of the blower-ON
delay period.
The indoor
fan motor
will revert
to continuous-blower
airflow
after the gas heating
cycle is completed.
When the UI "calls for cooling",
the indoor
fan motor will switch
to operate
at cooling
airflow. When the call for cooling
is satisfied,
the indoor
fan motor
will operate
an additional
90 seconds
at
cooling
airflow
before
transitioning
back
to continuous-blower
airflow.
When
the call for continuous
fan is removed,
the indoor
blower
will continue
operating
for an additional
5 seconds
before shutting
down, if no other function
requires
blower
motor operation.
COMPONENT
TEST
The Infinity Furnace
Board features
a gas component
test system
to
help diagnose
a system
problem
in the case of a gas component
failure.
To initiate
the component
test procedure,
ensure
that there
are no UI inputs
to the control
(the ABCD
connector
can be
removed
from the Infinity
control
board for this operation)
and all
time delays have expired.
Turn on setup switch
SWl-6.
NOTE:
The component
test feature
will not operate
if the control
is receiving
any UI signals
or until all time delays have expired.
The component
test sequence
is as follows:
1. The control
turns the inducer
motor ON and keeps
it ON
through
step 3.
2. After waiting
10 seconds,
the control
turns the igniter
ON
for 15 seconds,
then OFF.
3. The control
then
turns
the
indoor
fan motor
on for 15
seconds,
then OFF.
4. After
shutting
the blower
motor
OFF, the control
runs the
inducer
for 10 seconds,
then turns it OFF.
NOTE:
The EAC terminals
are energized
when
the blower
is
operating.
After
the component
test is completed,
one or more
status codes
(11, 25, or 41) will flash.
See component
test section
or Status
Code Label for explanation
of status codes.
NOTE:
To repeat
component
test, turn setup switch
SWl-6
to
OFF and then back ON.
Check
for Refrigerant
Leaks
Locate
and repair refrigerant
leaks and charge the unit as follows:
1. Use both
high-
and low-pressure
ports to relieve
system
pressure
and reclaim remaining
refrigerant.
2. Repair leak following
accepted
practices.
NOTE:
Install a filter drier whenever
the system
has been opened
for repair.
3. Check system
for leaks using an approved
method.
4. Evacuate
refrigerant
system
and reclaim
refrigerant
if no
additional
leaks are found.
5. Charge
unit
with
Puron
(R-410A)
refrigerant,
using
a
volumetric-charging
cylinder
or accurate
scale.
Refer
to
unit rating plate for required
charge.
Start-Up
Adjustments
Complete
the
required
procedures
given
in
the
Pre-Start-Up
section
before
starting
the unit. Do not jumper
any safety devices
when
operating
the unit. Do not operate
the unit in cooling
mode
when
the
outdoor
temperature
is below
40°F
(4°C)
(unless
low-ambient
operation
is enabled
in the UI). Do not rapid
cycle
the
compressor.
Allow
5 min.
between
"on"
cycles
to prevent
compressor
damage.
CHECKING
COOLING
AND
HEATING
CONTROL
OPERATION
See UI Installation
Instructions
for detailed
system
CHECKOUT.
CHECKING
AND ADJUSTING
REFRIGERANT
CHARGE
The
refrigerant
system
is fully
charged
with
Puron
(R-410A)
refrigerant
and is tested and factory sealed.
NOTE:
Any adjustment
to refrigerant
charge must be done with
unit operating
in HIGH
stage.
NOTE:
Adjustment
of the refrigerant
charge
is not required
unless
the unit
is suspected
of not
having
the
proper
R-410A
charge.
The charging
label and the tables
shown
refer to system
temperatures
and pressures
in cooling
mode
only.
A refrigerant
charging
label is attached
to the outside
of the unit.
25

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents