INPUTS
Demand Control
Ventilation (DCV)
Below set
High
(DCV LED Off)
(Free Cooling LED Off)
Low
(Free Cooling LED On)
Above set
High
(DCV LED On)
(Free Cooling LED Off)
Low
(Free Cooling LED On)
*For single enthalpy control, the module compares outdoor
enthalpy to the ABCD set point.
†Power at N terminal determines Occupied/Unoccupied setting:
24 vac (Occupied), no power (Unoccupied).
**Modulation is based on the supply air sensor signal.
††Modulation is based on the DCV signal.
***Modulation is based on the greater of DCV and supply-air sen-
sor signals, between minimum position and either maximum
position (DCV) or fully open (supply-air signal).
†††Modulation is based on the greater of DCV and supply-air
sensor signals, between closed and either maximum position
(DCV) or fully open (supply-air signal).
Table 30 — EconoMi$erIV Input/Output Logic
Enthalpy*
Y1
Outdoor
Return
Low
On On
On Off
Off Off
High
On On
On Off
Off Off
Low
On On
On Off
Off Off
High
On On
On Off
Off Off
Compressor
Y2
Stage
Stage
1
2
On
On
Minimum position
On
Off
Off
Off
On
Off
Modulating** (between min.
position and full-open)
Off
Off
Off
Off
Minimum position
On
On
Modulating†† (between min.
position and DCV maximum)
On
Off
Off
Off
On
Off
Modulating***
Off
Off
Off
Off
54
OUTPUTS
N Terminal†
Occupied
Unoccupied
Damper
Closed
Modulating** (between
closed and full-open)
Closed
Modulating†† (between
closed and DCV
maximum)
Modulating†††