Carrier 48TM016-028 Installation, Start-Up And Service Instructions Manual page 15

Single-package rooftop units electric cooling/gas heating
Table of Contents

Advertisement

VOLTAGE
NOMINAL
UNIT
RANGE
VOLTAGE
48TM
(3 Ph, 60 Hz)
Min
Max RLA LRA RLA LRA RLA LRA Qty Hp FLA (ea)
208/230
187
253
016
460
414
508
575
518
633
208/230
187
253
020
460
414
508
575
518
632.5 12.1
208/230
187
253
025
460
414
508
575
518
633
208/230
187.2
253
028
460
414
508
575
517.5 632.5
LEGEND
FLA
— Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
IFM
— Indoor (Evaporator) Fan Motor
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC
— National Electrical Code
OFM
— Outdoor (Condenser) Fan Motor
RLA
— Rated Load Amps
*Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combination
load equipment (refer to NEC Articles 430 and 440), the overcurrent pro-
tective device for the unit shall be fuse or HACR breaker. Canadian units
may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is
greater than 2%. Use the following formula to determine the percent
voltage imbalance.
% Voltage Imbalance
max voltage deviation from average voltage
= 100 x
average voltage
Table 5 — Electrical Data
COMPRESSOR
No. 1
No. 1A
No. 2
32.1 195
20.7
156
16.4
95
10
70
12
80
8.2
54
30.1 225
28.8
195
15.5 114
14.7
95
80
10.7
80
42
239
33.6
225
19.2 125
17.3
114
13.8 80.0
13.5 80.0
20.7 156 20.7 156
47.1
245
10
75
10
75
19.6
125
8.2
54
8.2
54
15.8
100
OFM
IFM
Hp
FLA
3
0.5
1.7
5.0 15.8/15.8
3
0.5
0.8
5.0
7.9
3
0.5
0.75
5.0
6.0
3
0.5
1.7
5.0 15.8/15.8
3
0.5
0.8
5.0
7.9
3
0.5
0.75
5.0
6.0
2
1
6.6
7.5 25.0/25.0
2
1
3.3
7.5
13.0
2
1.0
3.4
7.5
10.0
6
0.5
1.7
10.0 28.0/28.0
6
0.5
0.8
10.0
14.6
6
0.5
0.8
10.0
13.0
EXAMPLE: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
Average Voltage = 452 + 464 + 455
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent voltage imbalance.
% Voltage Imbalance = 100 x
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%,
contact your local electric utility company immediately.
15
POWER
COMBUSTION
EXHAUST
FAN MOTOR
FLA LRA
FLA
MCA
0.57
82/82
4.6
18.8
0.57
86/86
0.30
41
2.3
6.0
0.30
43
0.57
31
2.1
4.8
0.57
34
0.57
87/87
4.6
18.8
0.57
92/92
0.30
44
2.3
6.0
0.30
47
0.57
34
2.1
4.8
0.57
36
0.57
124/124 150/150
4.6
18.8
0.57
129/129 150/150
0.30
61
2.3
6.0
0.30
63
0.57
48
2.1
4.8
0.57
50
0.57
138/138 175/175
4.6
18.8
0.57
143/143 150/175
0.30
64
2.3
6
0.30
66
0.57
54
2.1
4.8
0.57
56
3
1371
=
3
= 457
7
457
POWER
SUPPLY
MOCP*
110/110
110/110
50
50
40
40
110/110
110/110
50
60
40
40
80
80
60
60
80
80
60
70