VOLTAGE
NOMINAL
UNIT
RANGE
VOLTAGE
48TM
(3 Ph, 60 Hz)
Min
Max RLA LRA RLA LRA RLA LRA Qty Hp FLA (ea)
208/230
187
253
016
460
414
508
575
518
633
208/230
187
253
020
460
414
508
575
518
632.5 12.1
208/230
187
253
025
460
414
508
575
518
633
208/230
187.2
253
028
460
414
508
575
517.5 632.5
LEGEND
FLA
— Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
IFM
— Indoor (Evaporator) Fan Motor
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC
— National Electrical Code
OFM
— Outdoor (Condenser) Fan Motor
RLA
— Rated Load Amps
*Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combination
load equipment (refer to NEC Articles 430 and 440), the overcurrent pro-
tective device for the unit shall be fuse or HACR breaker. Canadian units
may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is
greater than 2%. Use the following formula to determine the percent
voltage imbalance.
% Voltage Imbalance
max voltage deviation from average voltage
= 100 x
average voltage
Table 5 — Electrical Data
COMPRESSOR
No. 1
No. 1A
No. 2
32.1 195
—
—
20.7
156
16.4
95
—
—
10
70
12
80
—
—
8.2
54
30.1 225
—
—
28.8
195
15.5 114
—
—
14.7
95
80
—
—
10.7
80
42
239
—
—
33.6
225
19.2 125
—
—
17.3
114
13.8 80.0
—
—
13.5 80.0
20.7 156 20.7 156
47.1
245
10
75
10
75
19.6
125
8.2
54
8.2
54
15.8
100
OFM
IFM
Hp
FLA
3
0.5
1.7
5.0 15.8/15.8
3
0.5
0.8
5.0
7.9
3
0.5
0.75
5.0
6.0
3
0.5
1.7
5.0 15.8/15.8
3
0.5
0.8
5.0
7.9
3
0.5
0.75
5.0
6.0
2
1
6.6
7.5 25.0/25.0
2
1
3.3
7.5
13.0
2
1.0
3.4
7.5
10.0
6
0.5
1.7
10.0 28.0/28.0
6
0.5
0.8
10.0
14.6
6
0.5
0.8
10.0
13.0
EXAMPLE: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
Average Voltage = 452 + 464 + 455
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent voltage imbalance.
% Voltage Imbalance = 100 x
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%,
contact your local electric utility company immediately.
15
POWER
COMBUSTION
EXHAUST
FAN MOTOR
FLA LRA
FLA
MCA
—
—
0.57
82/82
4.6
18.8
0.57
86/86
—
—
0.30
41
2.3
6.0
0.30
43
—
—
0.57
31
2.1
4.8
0.57
34
—
—
0.57
87/87
4.6
18.8
0.57
92/92
—
—
0.30
44
2.3
6.0
0.30
47
—
—
0.57
34
2.1
4.8
0.57
36
—
—
0.57
124/124 150/150
4.6
18.8
0.57
129/129 150/150
—
—
0.30
61
2.3
6.0
0.30
63
—
—
0.57
48
2.1
4.8
0.57
50
—
—
0.57
138/138 175/175
4.6
18.8
0.57
143/143 150/175
—
—
0.30
64
2.3
6
0.30
66
—
—
0.57
54
2.1
4.8
0.57
56
3
1371
=
3
= 457
7
457
POWER
SUPPLY
MOCP*
110/110
110/110
50
50
40
40
110/110
110/110
50
60
40
40
80
80
60
60
80
80
60
70