Siemens FDUD293 Technical Manual page 44

Intelligent detector tester
Table of Contents

Advertisement

5
Operation
Deviation list
No.
Display text on service
device
85
In 4 void par
86
In 4 problem 1
87
In 4 problem 2
88
In 4 problem 3
89
In 4 trouble 1
90
In 4 trouble 2
91
In 4 trouble 3
92
B4 diff Line
93
B4 unstab. Line
94
B4 res.
95
B4 open line
96
B4 short circuit
97
B4 earth ending
98
Out A no par
99
Out A trouble
100
Out A void par
101
Out B no par
102
Out B trouble
103
Out B void par
104
Out C no par
105
Out C trouble
106
Out C void par
107
Out D no par
108
Out D trouble
109
Out D void par
110
maybe excha.
111
advice excha.
112
needed excha.
113
turn FDUD one quarter
114
and retry
44
Building Technologies
Fire Safety
Meaning
Incorrect parameter setting
External problem 1, depends on device type
External problem 2, depends on device type
External problem 3, depends on device type
External fault 1, depends on device type
External fault 2, depends on device type
External fault 3, depends on device type
Deviation on line resistance
Unstable line resistance
Reserved
Open line
Short-circuit
Reserved (earth fault)
No parameter setting or deviation on output
Action is not performed, hardware fault
Invalid parameter setting or fault on detector line
No parameter setting or deviation on output
Action is not performed, hardware fault
Invalid parameter setting or fault on detector line
No parameter setting or deviation on output
Action is not performed, hardware fault
Invalid parameter setting or fault on detector line
No parameter setting or deviation on output
Action is not performed, hardware fault
Invalid parameter setting or fault on detector line
Observe information
Replacement recommended
Replacement necessary
Rotate the service device 90° and execute the command again.