Cabling of the devices
A
WeCo
B
B
Xtender Bottom Side
A- CAN Port 1 of the Inverter RJ45 Port
B- CAN Port 2 of the inverter RJ45 Port
Termination Switch to the
right of the two RJ45 Ports
T
O
Set Switch to the right.
Xcom-CAN COM Bus Side
B- CAN Port 2 of the inverter to RG45 COM
Port 1 of Xcom
COM Port 2 of Xcom remains empty
Termination Switch to the
right of the two RJ45 Ports
T
O
Set Switch to the left.
LED GREEN
● Make sure the LED blinks 2 times- interval and repeats.
● If the LED blinks Green + RED check the connection
again because the communication is not correct.
● If the LED is RED the connection is wrong.