Carrier 38AU Installation, Start-Up And Service Instructions Manual page 22

Air cooled condensing units 60 hz with puronr (r-410a) refrigerant
Table of Contents

Advertisement

NOMINAL
POWER
UNIT
SUPPLY
SIZE
38AU
V--- Ph--- Hz
208/230---3---60
D*16
460 ---3 ---60
Z*16
575 ---3 ---60
208/230---3---60
D*25
460 ---3 ---60
Z*25
575 ---3 ---60
NOMINAL
POWER
UNIT
SUPPLY
SIZE
38AU
V--- Ph--- Hz
208/230---3---60
D*16
460 ---3 ---60
Z*16
575 ---3 ---60
208/230---3---60
D*25
460 ---3 ---60
Z*25
575 ---3 ---60
Legend and Notes for Table 10
LEGEND:
BRKR
--- Circuit breaker
CO
--- Convenient outlet
FLA
--- Full Load Amps
LRA
--- Locked Rotor Amps
MCA
--- Minimum Circuit Amps
Protection
NEC
--- National Electrical Code
PWRD CO
--- Powered convenient outlet
RLA
--- Rated Load Amps
UNPWR CO
--- Unpowered convenient outlet
NOTES:
1. In compliance with NEC requirements for multimotor and
combination load equipment (refer to NEC Articles 430 and
440), the overcurrent protective device for the unit shall be
fuse or HACR breaker. Canadian units may be fuse or circuit
breaker.
2. The MCA values are calculated in accordance with The NEC.
Article 440.
3. Motor RLA and LRA values are established in accordance
with Underwriters' Laboratories (UL). Standard 1995.
4. The 575--- v units are UL, Canada--- listed only.
5. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply
voltage is greater than 2%. Use the following formula to de-
termine the percentage of voltage imbalance.
Table 10 – Unit Wire/Fuse or HACR Breaker Sizing Data
COMPRESSOR
VOLTAGE
RANGE
No. 1
Min
Max
RLA
LRA
RLA
187
253
25.0
164
25.0
414
506
12.2
100
12.2
518
633
9.0
78
9.0
187
253
30.1
225
30.1
414
506
16.7
114
16.7
518
633
12.2
80
12.2
COMPRESSOR
VOLTAGE
RANGE
No. 1
Min
Max
RLA
LRA
RLA
187
253
25.0
164
25.0
414
506
12.2
100
12.2
518
633
9.0
78
9.0
187
253
30.1
225
30.1
414
506
16.7
114
16.7
518
633
12.2
80
12.2
NO C.O. or UNPWRD C.O.
No. 2
OFM
POWER SUPPLY
FLA
LRA
Qty
MCA
(ea)
164
3
1.5
60.8/60.8
100
3
0.8
29.9
78
3
0.7
22.4
225
4
1.5
73.7/73.7
114
4
0.8
40.8
80
4
0.7
30.3
No. 2
OFM
POWER SUPPLY
FLA
LRA
Qty
MCA
(ea)
164
3
1.5
65.6/65.6
100
3
0.8
32.1
78
3
0.7
24.1
225
4
1.5
78.5/78.5
114
4
0.8
43
80
4
0.7
32
Example: Supply voltage is 230-3-60
% Voltage Imbalance
= 100 x
AB = 224 v
BC = 231 v
AC = 226 v
(224 + 231 + 226)
Average Voltage =
=
Determine maximum deviation from average voltage.
(AB) 227 – 224 = 3 v
(BC) 231 – 227 = 4 v
(AC) 227 – 226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.
% Voltage Imbalance
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.
22
DISCONNECT SIZE
FUSE or
HACR
FLA
LRA
BRKR
80/80
63/63
337/337
40
31
206
30
23
162
100/100
76/76
462/462
50
42
236
40
31
168
w/ PWRD C.O.
DISCONNECT SIZE
FUSE or
HACR
FLA
LRA
BRKR
90/90
68/68
342/342
40
33
208
30
25
164
100/100
82/82
467/467
50
45
238
40
33
170
max voltage deviation from average voltage
average voltage
=
3
227
4
= 100 x
227
= 1.76%
681
3

Advertisement

Table of Contents
loading

This manual is also suitable for:

38au series38auz 16 series38aud 16 series38auz 25 series38aud 25 series