Power Cable Entry; Field Control Wiring; 24 V Power Reserve For The User - Carrier AquaForce PUREtec 61XWHLZE 03 Installation, Operation And Maintenance Manual

High temperature water-source heat pump with r1234ze(e)
Table of Contents

Advertisement

5 - ELECTRICAL CONNECTION
Connectable
wire section
61XWHLZE / 61XWH-ZE
Circuit(s) A(/B)
mm² (per phase)
Model
3
5
7
10
2 x 240/2 x 240
14
2 x 300/2 x 300
15
2 x 300/2 x 300
17
2 x 300/2 x 300
Model with option 81
10
14
15
17
61XWHHZE
Model
3
5
7
10
2 x 240/2 x 240
15
2 x 240/2 x 240
Model with option 81
10
(1)  Connection capacities actually available for each machine, defined according to the connection terminal size, the control box access opening size and the available 
space inside the control box.
(2) Selection simultation result considering the hypothesis indicated.
(3)  If the maximum calculated section is for an XLPE cable type or specified "not compatible", this means that it exists a risk to exceed the real connection capacity available. 
Special attention must be given to the selection.
Note:
The currents considered are given for a machine equipped with a hydronic kit operating at maximum current.

5.5 - Power cable entry

The power cables can enter the unit control box from above the
unit. A removable aluminium plate on the upper part of the control
box  face  allows  introduction  of  the  cables.  Refer  to  the  certified 
dimensional drawing for the unit.
The plate fixing on the electrical box as well as the cable passage 
through the plate have to be tight.
If not, the differential pressure sensor
electrical box fan operating. This will prevent the unit from starting.

5.6 - Field control wiring

IMPORTANT: Field connection of interface circuits may lead
to safety risks: any control box modification must maintain
equipment conformity with local regulations. Precautions
must be taken to prevent accidental electrical contact between
circuits supplied by different sources:
The routing selection and/or conductor insulation
characteristics must ensure dual electric insulation.
In case of accidental disconnection, conductor fixing between
different conductors and/or in the control box prevents any
contact between the conductor ends and an active energised
part.
Table of minimum and maximum connectable wire sections.
Calculation favourable case:
Perforated horizontal conduit
(standardised routing No. 15)
(1)
XLPE insulated cable
Section
Section
(2)
mm² (per phase)
1x 240
1 x 95
2 x 240
1 x 185
2 x 240
2 x 120
1 x 240/1 x 240
2 x 150/2 x 150
2 x 150/2 x 150
2 x 150/2 x 150
4 x 240
2 x 240
4 x 300
4 x 150
4 x 300
4 x 150
4 x 300
4 x 150
1 x 240
1 x 95
2 x 240
1 x 240
2 x 240
2 x 150
1 x 240/1 x 240
2 x 185/2 x 185
4 x 240
2 x 185
should not detect the
Max.length
Cable type
m
217
XLPE Cu
243
XLPE Cu
211
XLPE Cu
251/251
XLPE Cu
203/203
XLPE Cu
294/294
XLPE Cu
211/211
XLPE Cu
251
XLPE Cu
203
XLPE Cu
294
XLPE Cu
211
XLPE Cu
200
XLPE Cu
277
XLPE Cu
234
XLPE Cu
231/231
XLPE Cu
215/215
XLPE Cu
215
XLPE Cu
Refer to the Touch Pilot Control manual and the certified wiring 
diagram supplied with the unit for the field control wiring of the 
following features:
• Customer interlock
• Remote on/off switch
• Demand limit external switch
• Remote dual set point
• Alarm, alert and operation report
• Evaporator pump control
• Heat reclaim condenser pump control (option)
• Hot water valve control (option)
• Various interlocks on the Energy Management Module
(EMM) board (accessory or option)
CCN bus connection
• The permanent connection to the system CCN bus is made
at the terminal provided for this purpose inside the control
box.
• The connection of the CCN service tool is possible at a
socket under the control box, accessible from outside.
All panel feedthrough of control cables have to be tight to allow
electrical box fan operating detection.

5.7 - 24 V power reserve for the user

Control circuit reserve:
After all required options have been connected, the TC transformer
includes  a  power  reserve  that  can  be  used  for  the  field  control 
wiring: 2 A (24 V a.c.) or 48 VA.
Calculation unfavourable case:
Closed conduit
(standardised routing No. 41)
PVC insulated cable, if possible
Section
Max. length
(2)
mm² (per phase)
m
1 x 185
390
2 x 185
418
2 x 185
294
2 x 240/2 x 240
366/366
2 x 300/2 x 300
294/294
2 x 300/2 x 300
294/294
2 x 300/2 x 300
305/305
4 x 240
377
4 x 300
294
4 x 300
294
4 x 300
305
1 x 185
358
2 x 185
386
2 x 240
328
2 x 185/2 x 185
302
Not compatible
4 x 185
302
Cable type
(3)
PVC Cu
PVC Cu
XLPE Cu
PVC Cu
XLPE Cu
XLPE Cu
XLPE Cu
PVC Cu
XLPE Cu
XLPE Cu
XLPE Cu
PVC Cu
PVC Cu
XLPE Cu
XLPE Cu
XLPE Cu
17