Peripheral devices
Selecting the breaker/magnetic contactor
Check the model of the inverter and the converter unit you purchased. Appropriate peripheral devices must be selected
according to the capacity.
Refer to the table below to prepare appropriate peripheral devices.
• One circuit breaker and one magnetic contactor in total in a system
Motor
Number of
capacity
units
(kW)

630
2
710
2
800
2
900
2
945
3
1065
3
1200
3
1350
3

The motor output indicates the output power of a 4-pole motor at 400 VAC 50 Hz driven by all of the inverters in parallel connection.

Select an MCCB according to the power supply capacity.
For the use in the United States or Canada, provide the appropriate UL and cUL listed fuse that is suitable for branch circuit protection. (Refer to
page
109.)

The magnetic contactor is selected based on the AC-1 class. The electrical durability of magnetic contactor is 500,000 times. When the
magnetic contactor is used for emergency stops during motor driving, the electrical durability is 25 times.
If using an MC for emergency stop during driving the motor, select an MC regarding the converter unit input side current as JEM1038-AC-3 class
rated current. When using an MC on the inverter output side for commercial-power supply operation switching using a general-purpose motor,
select an MC regarding the rated motor current as JEM1038-AC-3 class rated current.

An air circuit breaker is also applicable in a system in which a 2000 A breaker or higher is applicable.
• One circuit breaker and one magnetic contactor per converter unit
Motor
Number of
output
units
(kW)

630
2
710
2
800
2
900
2
945
3
1065
3
1200
3
1350
3

The motor output indicates the output power of a 4-pole motor at 400 VAC 50 Hz driven by all of the inverters in parallel connection.

Select an MCCB according to the power supply capacity.
For the use in the United States or Canada, provide the appropriate UL and cUL listed fuse that is suitable for branch circuit protection. (Refer to
page
109.)

The magnetic contactor is selected based on the AC-1 class. The electrical durability of magnetic contactor is 500,000 times. When the
magnetic contactor is used for emergency stops during motor driving, the electrical durability is 25 times.
If using an MC for emergency stop during driving the motor, select an MC regarding the converter unit input side current as JEM1038-AC-3 class
rated current. When using an MC on the inverter output side for commercial-power supply operation switching using a general-purpose motor,
select an MC regarding the rated motor current as JEM1038-AC-3 class rated current.
NOTE
• When the breaker on the converter unit's input side trips, check for the wiring fault (short circuit), damage to internal parts of
the inverter and the converter unit, etc. The cause of the trip must be identified and removed before turning ON the power of
the breaker.
14
INSTALLATION AND WIRING
Converter unit
FR-CC2-[ ]-P
H400K
H450K
H500K
H560K
H400K
H450K
H500K
H560K
Applicable
Molded case circuit breaker (MCCB)
converter unit
FR-CC2-[ ]-P
H400K
900 A
H450K
1000 A
H500K
1200 A
H560K
1500 A
H400K
900 A
H450K
1000 A
H500K
1200 A
H560K
1500 A
Molded case circuit breaker (MCCB)
or earth leakage circuit breaker (ELB)
(type NF or NV)
1500 A
1600 A
1800 A
2100 A

2200 A

2400 A

2700 A

3100 A

(NF type)

 
Input-side magnetic
contactor

1300 A rated product
1400 A rated product
1600 A rated product
1800 A rated product
1900 A rated product
2100 A rated product
2400 A rated product
2700 A rated product
Input-side magnetic

contactor

S-N800
1000 A rated product
1000 A rated product
1200 A rated product
S-N800
1000 A rated product
1000 A rated product
1200 A rated product