Common specifications
Surrounding air
temperature
Surrounding air humidity
Storage temperature

Atmosphere
Altitude/vibration

Available only when a vector control compatible option is mounted.

In the initial setting, it is limited to 150% by the torque limit level.

Temperature applicable for a short time, e.g. in transit.

For the installation at an altitude above 1000 m (up to 2500 m), consider a 3% reduction in the rated current per altitude increase of 500 m.

This protective function is not available in the initial status.
102
SPECIFICATIONS
-10°C to +50°C (non-freezing)
95% RH or less (non-condensing) (With circuit board coating (conforming to IEC60721-3-3 3C2/3S2))
90% RH or less (non-condensing) (Without circuit board coating)
-20°C to +65°C
Indoors (without corrosive gas, flammable gas, oil mist, dust and dirt, etc.)
2
Maximum 1000 m, 2.9 m/s
or less
at 10 to 55 Hz (directions of X, Y, Z axes)
