FB2100/FB2200 Flow Computer CPU Enclosure & Electronics Field Replacement Guide
D301803X012
November 2020

Removing the HMI Module

1.
2.

Replacing the HMI Module

1.
2.
6
Use a #1 Phillips-head screwdriver to loosen the four captive fastening screws that attach the
HMI module to the CPU enclosure cover.
Captive Screws
Grasp the HMI module and remove it by gently pulling it straight out.
To replace the HMI module, line up the printed circuit board (PCB) with the slot on the back
and gently press it back on.
Tighten the four captive fastening screws with a torque value of 4 to 6 in.-lbs. (0.5 to 0.7 N-
m).