Download Print this page

Carrier 00EFN900003000A Installation Instructions Manual page 2

Remote cooler accessory 60 hz

Advertisement

ACCESSORY PACKAGE
PART NO.
00EFN900003000A
00EFN900003100A
Choose a space that can support the weight of the cooler and
economizer with service clearances and area for refrigerant
piping. Field-supplied piping must be limited to less than
50 lineal ft (15.25 m) or 75 equivalent ft (22 m) in length.
Suction and liquid line risers must be limited to less than 15 ft
(4.5 m) vertical riser elevation. Suction lines and economizer
lines must be insulated to prevent condensation. Relocating the
cooler introduces minimal line losses if correct piping practices
are followed. Buried lines are not permitted.
The remote cooler system can be applied in three different
configurations. See Fig. 1-3. In Fig. 1, the remote cooler and
the outdoor unit are at the same elevation. The suction, liquid,
and economizer lines run parallel between the cooler and the
outdoor unit. In Fig. 2, the outdoor unit and remote cooler are
at the same elevation, but the interconnecting piping has an ele-
vation of up to 15 ft (4.5 m) above the base elevation of the
cooler. This could be result of running piping over a wall or
through the ceiling in a building. In Fig. 3, the remote cooler is
located below the outdoor unit. The interconnecting piping has
an elevation of up to 15 ft (4.5 m) above the base elevation of
the remote cooler. This could occur if the remote cooler is in-
stalled in a basement.
NOTE: Unit 30XA refrigeration piping can be either copper
tubing or steel tubing with flanged connections. All units are
Table 2 — Accessory Package Contents
ITEM NO.
1
Economizer shutoff valve - 1
2
Liquid line shutoff valve - 1
3
5 Wire jacketed cable
4
5
6
Junction box cover
7
8
Cooler pipe flange - 3
10
Flex connector flange - 4 in. (102 mm)
11
Loose pipe flange - 4 in. (102 mm)
12
Cooler flange O-ring
13
Flex connector flange O-ring
14
Compressor flange gasket - 3 in. (76 mm)
15
Compressor flange gasket - 4 in. (102 mm)
16
Transducer wiring harness - 100 ft (30.5 m)
1
Economizer shutoff valve - 1
2
Liquid line shutoff valve - 1
3
5 Wire jacketed cable
4
5
6
Junction box cover
7
8
Flex connector flange O-ring
9
Compressor flange gasket - 4 in. (102 mm)
10
Compressor flange gasket - 5 in. (127 mm)
11
Loose pipe flange - 5 in. (127 mm)
12
Loose pipe flange - 4 in. (102 mm)
13
Flex connector flange - 4 in. (102 mm)
14
Transducer wire harness - 100 ft (30.5 m)
DESCRIPTION
1
/
in. (29 mm)
8
3
/
in. (35 mm)
8
Cable assembly
Junction box
M6 Screws
1
/
in. (79 mm)
8
1
/
in. (29 mm)
8
3
/
in. (35 mm)
8
Cable assembly
Junction box
M6 Screws
factory charged with compressor oil to the required level.
However, when the double riser is constructed with U-bends or
street elbows, a substantial amount of oil can be trapped in the
U-bend during prolonged minimum load operation. If this
occurs, additional oil is needed to add to the system to prevent
the oil level from dropping below the minimum level in the oil
separator. Add 1 gallon of oil to each circuit. Refer to Controls,
Start-up, Operation, Service, and Troubleshooting Guide for
recommended oil type.
Table 3A — Refrigeration Piping and
Connections Material (English)
PIPE SIZE (in.)
5
7
1
/
,
/
, 1
/
, 1
8
8
8
1
5
2
/
, 2
/
, 3
8
8
1
2, 2
/
, 3, 3
2
Table 3B — Refrigeration Piping and
Connections Material (SI)
PIPE SIZE (mm)
16, 22, 29, 35, 41, 54, 67, 79
51, 64, 76, 89, 102
2
PART NO.
00PPG000023501A
EP71BA393
RM02EJ200
32GB404694
HX30FZ001
HX38ZZ001
00PPN500000302A
00PSN500091400A
00PSG000213300A
00PSG000205100A
KK71EW256
KK71EW250
00PPG000011702A
00PSG000011703A
00PSN500180500A
00PPG000023501A
EP71BA393
RM02EJ200
32GB404694
HX30FZ001
HX38ZZ001
00PPN500000302A
KK1EW250
00PSG000011703A
00PPG000011704A
00PSG000211900A
00PSG000205100A
00PSG000213300A
00PSN500180500A
MATERIAL
3
5
/
, 1
/
,
8
8
Refrigeration copper
1
/
8
1
/
, 4
Schedule 40 Steel
2
MATERIAL
Refrigeration copper
Schedule 40 Steel
QTY
2
2
200 ft
(61 m)
5
2
2
8
2
2
2
4
2
2
4
2
2
2
200 ft
(61 m)
5
2
2
8
2
4
4
2
2
2
2

Advertisement

loading