Carrier 42TGF CP Series Installation Manual

Under seiling air conditioner
Hide thumbs Also See for 42TGF CP Series:

Advertisement

Under eili
c
ng a
ir conditioner
Model name:
4
2T
GF____CP
Notice:
quality and reliability standards, and to meet local regulations and market requirements.
All features and specifications are subject to change without prior notice.
is committed to continuously improving its products to ensure the highest
Installation
Manual
1115652934
English
Installation Manual
1
English
Portuguê
2
5

Advertisement

Table of Contents
loading

Summary of Contents for Carrier 42TGF CP Series

  • Page 1 1115652934 Under eili ng a ir conditioner Model name: GF____CP Installation Manual Notice: is committed to continuously improving its products to ensure the highest quality and reliability standards, and to meet local regulations and market requirements. All features and specifications are subject to change without prior notice. English Installation Manual English...
  • Page 2: Table Of Contents

    – 1 – Contents Original instruction Please read this Installation Manual carefully before installing the Air Conditioner. 1 Precautions for safety ..........4 This Manual describes the installation method of the indoor unit.
  • Page 3 Thank you for purchasing this air conditioner. Definition of Protective Gear Please read carefully through these instructions that contain important information which complies with the When the air conditioner is to be transported, installed, maintained, repaired or removed, wear protective gloves Machinery Directive (Directive 2006/42/EC), and ensure that you understand them.
  • Page 4 – 3 – Warning indications on the air conditioner unit WARNING WARNING ELECTRICAL SHOCK HAZARD ELECTRICAL SHOCK HAZARD Disconnect all remote Disconnect all remote electric power supplies before servicing. electric power supplies before servicing. WARNING WARNING Moving parts. Moving parts. Do not operate unit with grille removed.
  • Page 5: Precautions For Safety

    • Before opening the intake grille, set the circuit breaker to the OFF Precautions for safety position. Failure to set the circuit breaker to the OFF position may result in injury through contact with the rotation parts. Only a quali ed The manufacturer shall not assume any liability for the damage caused installer or quali ed service person...
  • Page 6 – 5 – If the gas leak and accumulate around the unit, it may ignite and cause Refrigerant piping a fi re. • Install the refrigerant pipe securely during the installation work before • Install the indoor unit at least 2.5 m above the fl oor level since operating the air conditioner.
  • Page 7 Explanations given to user • After completing the repair or relocation work, check that the earth wires are connected properly. • Upon completion of the installation work, tell the user where the • Install a circuit breaker that meets the specifi cations in the installation circuit breaker is located.
  • Page 8: Accessory Parts

    – 7 – Accessory parts Selection of installation place Avoid installing in the following places. ’ Select a location for the indoor unit where the cool or warm air will circulate evenly. Installation Manual This manual (Hand over to customers) Avoid installation in the following kinds of locations.
  • Page 9: Installation

    Installation Installation space (Unit: mm) Reserve sufficient space required for installation or service work. CAUTION Strictly comply with the following rules to prevent damage of the indoor units and human injury. Do not put a heavy article on the indoor unit or let a person get on it. (Even units are packaged) Carry in the indoor unit as it is packaged if possible.
  • Page 10 – 9 – Installation of hanging bolt Before installation Installation of hanging bolt CAUTION Use M10 hanging bolts (4 pcs, locally procured). Consider the piping / wiring after the unit is hung to Matching to the existing structure, set pitch according determine the location of the indoor unit installation to size in the "External dimensions".
  • Page 11 Draw-out direction of pipe / Installation of indoor unit Holding down of main unit <In case of taking pipe from upper side> Taking pipe from upper side is applied only to the wire <Hanging the indoor unit directly from the refrigerant pipe.
  • Page 12: Drain Piping

    – 11 – Drain piping Attaching the hanging bracket Attach the indoor unit onto the hanging bracket and fasten it tight with the bolts and first screws. Remove the screws fastening hanging CAUTION bracket onto the indoor unit. Following the Installation Manual, perform the drain piping work so that water is properly drained. Apply a heat insulation so as not to cause a dew condensation.
  • Page 13 Connection of drain hose Heat insulating process Insert the attached drain hose into the drain pipe connecting port on the drain pan up to the end. Using the attached drain hose heat insulator, lap the connecting section and the drain hose without clearance, and then tighten with two handing band so that heat insulator does not open.
  • Page 14: Refrigerant Piping

    – 13 – Refrigerant piping Flaring diameter size: A (Unit: mm) Outer dia. of connecting Tightening torque pipe (mm) Outer dia. of copper pipe 14 to 18 (1.4 to 1.8 –0.4 CAUTION CAUTION CAUTION CAUTION 34 to 42 (3.4 to 4.2 IMPORTANT 4 POINTS FOR PIPING WORK 12.7 49 to 61 (4.9 to 6.1 kgf...
  • Page 15: Electrical Connection

    Electrical connection Open the valve fully Open the valve of the outdoor unit fully. A 4 mm- hexagonal wrench is required for opening the valve. For details, refer to the Installation Manual attached to WARNING the outdoor unit. Use the specified wires for wiring connect the terminals. Securely fix them to prevent external forces applied Gas leak check to the terminals from affecting the terminals.
  • Page 16 – 15 – Wiring between indoor unit and outdoor unit Connecting the system interconnection wire <Single connection> Figure below shows the wiring connections between the indoor and outdoor units and between the indoor units and Terminal block of Remote controller remote controller.
  • Page 17: Applicable Controls

    Applicable controls Installing indoor unit on high Each time button is pushed, indoor unit numbers in the control group change ceiling cyclically. Select the indoor unit to change Basic procedure for changing REQUIREMENT settings for. When the height of the ceiling to be installed exceeds settings The fan of the selected unit runs and the louvers When you use this air conditioner for the first time, it...
  • Page 18 – 17 – Filter sign setting Group control Push buttons simultaneously for at least 4 seconds to call the service monitor According to the installation condition, the filter sign Group control for system of multiple units mode. term (Notification of filter cleaning) can be changed. One remote controller can control maximum 8 indoor units as a group.
  • Page 19: Test Run

    Test run To recognize the position of the In the group control, every time corresponding indoor unit though the button is pushed, the indoor UNIT No. in the indoor UNIT No. is known group control is displayed in order. In this time, the position of the indoor unit can be Check the position during operation stop.
  • Page 20: Auto Restart Setting

    – 19 – Auto restart setting Wireless remote controller Checking remote transmission 1. Push the ON/OFF button on the remote controller to determine that it works properly. NOTE This product is designed so that, after a power failure, Pushing the TEMPORARY button once (for about Be sure to operate the unit, following the instruction it can restart automatically in the same operating mode one second) causes the...
  • Page 21: Maintenance

    Maintenance Auto restart (signal receiving unit) 1. Setting Press and hold down the TEMPORARY button for <Daily maintenance> Cleaning with water or vacuum cleaner. 3 to 10 seconds, and the unit will “Pi-pi”, while the If dust is heavy, wash it with tepid water operation light (green) blinks for 5 seconds.
  • Page 22: Troubleshooting

    – 21 – Troubleshooting Periodic Maintenance For environmental conservation, it is strongly recommended that the indoor and outdoor units of the air conditioner in use be cleaned and maintained regularly to ensure efficient operation of the air conditioner. When the air conditioner is operated for a long time, periodic maintenance (once a year) is recommended. Confirmation and check Confirmation of error log Furthermore, regularly check the outdoor unit for rust and scratches, and remove them or apply rustproof...
  • Page 23 Check codes and parts to be checked Wired Wireless remote controller remote Sensor block display of controller receiving unit display Judging Main defective parts Parts to be checked / error description conditioner Wired Wireless remote controller device remote status Operation Timer Sensor block display of controller Indication...
  • Page 24 Wired Wireless remote controller remote Sensor block display of controller receiving unit Judging display Main defective parts Parts to be checked / error description conditioner device status Operation Timer Indication Ready Flashing GR GR OR 4-way valve, indoor temp. sensors (TC/TCJ) --- An Outdoor Auto- error was detected due to temperature drop of the...
  • Page 25: Appendix

    Appendix 5. When a commercially available dryer is attached to the Work instructions existing pipes. The existing R22 and R410A piping can be reused for There is the possibility that copper green rust has inverter R32 product installations. been generated. Existing pipes: Cannot be used.
  • Page 26 ..........28 .
  • Page 27 Machinery Directive (Directive 2006/42/EC) • • • • • • • •...
  • Page 28 WARNING ELECTRICAL SHOCK HAZARD Disconnect all remote electric power supplies before servicing. WARNING Moving parts. Do not operate unit with grille removed. Stop the unit before the servicing. CAUTION High temperature parts. You might get burned when removing this panel. CAUTION Do not touch the aluminum fins of the unit.
  • Page 32 Ω HFC (R32) Ω...
  • Page 33 • • • – • M10 x Ø25 • • • (10 t × 190 × 190) • • (6 t × 120 × 160) • (n=4) (n=2) • • • • • •...
  • Page 34 • • • • 4.0 . 0131CP, 0181CP, 0241CP, 0301CP 4.3 . 0361CP, 0401CP, 0481CP, 0601CP 3.5 . “ ” Ø40) 0131CP, 0181CP, 0361CP, 0401CP, 0241CP, 0301CP 0481CP, 0601CP 3.5 . 3.5 . 0000 4.0 . 4.3 . 0003 Ø40) •...
  • Page 35 • (Ø100) • • • • • W3/8 • W3/8 M10 (4 “ • ” (Ø100) (Ø100)
  • Page 36 < > < > < > < > “ • ” < > < >...
  • Page 37 • • (1/100 • 20 . • • • • • • 1.5 . • 1/100 VP30 • 1/100 VP 20 VP20 ( Ø26 867 to 872 1184 to 1189 1501 to 1506...
  • Page 38 • • • • • • • . 10 •...
  • Page 39 ( .) 18 (1.4 1.8 kgf • -0.4 42 (3.4 4.2 kgf • 12.7 61 (4.9 6.1 kgf • 13.2 15.9 77 (6.3 7.7 kgf • 12.7 16.6 19.1 115 (9.5 11.5 kgf • 15.9 19.7 19.1 24.0 Ø6.35, Ø9.52, Ø12.7 Ø15.88 Ø19.1 ( .) Ø12.7...
  • Page 40 • • • 220 – 240 HFC (R32, R134a, R410A • • • • • 120 °C • • 4 × 1.5 . (H07RN-F 60245 IEC 66) 70 • × • : 2 × 0.5 500 . = L + L1 + L2 + … Ln 400 .
  • Page 41 < > • • 1 2 3 • • • • P.C.
  • Page 42 3.5 . • • → → → → → CODE No. [5d] • < > [SET DATA] “ • ” CODE No. [5d] • CODE No. [ “TEMP.” CODE No. SET DATA CODE No. • CODE No. SET DATA [ “TIME”...
  • Page 43 CODE No. TEMP. (CODE No.) → → → → → CODE No. [01] • [SET DATA] SET DATA • individual line ( “ ” • • SET DATA (A/B) (A/B) 0000 • 0001 CODE No. 2500 0002 (TA) 0003 5000 0004 10000 (TC)
  • Page 44 • 2, 4 500V Ω [TEST] Ω • [ Cool] • CODE No. [01] [ Cool] CODE No. [01] • • • ([TEST]...
  • Page 45 ON/OFF • • • • 0000: 0001: 0001: TEMPORARY TIME • •...
  • Page 46 < > • • • • • • • TEMPORARY • • •...
  • Page 47 • “ ” [01 : • CODE No. CHECK • • Unit No. • • • CODE No. CODE No. [01] ( • • [04] ( → • • •...
  • Page 48 (TA), P.C. (TA) (TA) TS (1) TS (1) IGBT P.C. (TE/TS) P.C. P.C. EEPROM P.C. P.C. P.C. EEPROM P.C. P.C. (Idc) IPDU-CDB P.C. AC-CT P.C. P.C. P.C. IPDU IPDU (TCJ), P.C. (TCJ) (TCJ) (TC), P.C. P.C. P.C. (TC) (TC) (TD), P.C.
  • Page 49 P.C. CN80 P.C. IGBT P.C. P.C. (TC/TCJ) --- P.C. IGBT, P.C. (G-Tr/IGBT) P.C. E03/L07/L03/L08 ALT : SIM : LEDs OR : GR :...
  • Page 50 㪋 · ·Õ è Í ‹ § Œ ª ã ¹ Ò ä ‹ Ù Â Í Ê ‹ Á Á Ò Ã Ò ª ã ¶ Œ ´ ä Œ Ë ã ª ã Œ ã Í ‹ · Œ ‹...
  • Page 52 Installation Manual Model name: 42TGF____CP 1115652934...

This manual is also suitable for:

0131cp0181cp0241cp0301cp0361cp0401cp ... Show all

Table of Contents