Specifications - SMC Networks PFMC Series User Manual

Table of Contents

Advertisement

PFMC
Series

Specifications

Model
Applicable fluid
Fluid
Fluid temperature range
Detection method
Rated flow range
Set flow
rate range
Flow
Minimum
setting unit
Accumulated volume per pulse
(Pulse width = 50 msec.)
Accumulated value hold function
Rated pressure range
Proof pressure
Pressure
Pressure loss
Pressure characteristics
Power supply voltage
Electrical
Current consumption
Protection
Display accuracy
Analog output accuracy
Accuracy
Repeatability
Temperature characteristics
Output type
Output mode
Switch operation
Maximum load current
Switch output
Maximum applied voltage (NPN only)
Internal voltage drop
(Residual voltage)
Response time
Hysteresis
Protection
Output type
Analog output
Note 5)
Impedance
Response time
External input
External input
Note 7)
Input mode
Reference condition
Unit
Note 9)
Displayable
range
Display
Minimum
display unit
Display
Indicator LED
Enclosure
Withstand voltage
Environmental
Insulation resistance
Operating temperature range
Operating humidity range
Standard
Piping specifications
Materials of parts in contact with fluid
Piping
specifications
Weight
Lead wire
Bracket
Note 1) When using the accumulated value hold function, use the operating
conditions to calculate the product life, and do not exceed it. The
maximum access limit of the memory device is 1 million cycles. If the
product is operated 24 hours per day, the product life will be as follows:
5 min interval: life is calculated as 5 min x 1 million = 5 million min = 9.5 years
2 min interval: life is calculated as 2 min x 1 million = 2 million min = 3.8 years
If the accumulated flow external reset is repeatedly used, the product
life will be shorter than calculated life.
Note 2) Do not release the OUT side piping port of the product directly to the
atmosphere without connecting piping. If the product is used with the
piping port released to atmosphere, accuracy may vary.
Note 3) The time from when the flow is changed by a step input (when the flow
280
A
Refer to pages 202 and 203 for Flow Switch Precautions. For details about the Specific Product
Precautions, refer to the Operation Manual on the SMC website, http://www.smcworld.com
PFMC7501
5 to 500 L/min
Instantaneous flow
5 to 525 L/min
Accumulated flow
Instantaneous flow
Accumulated flow
1 L/pulse
Note 1)
Note 2)
Select from Hysteresis, Window comparator, Accumulated output or Accumulated pulse output modes.
Note 3)
Note 4)
Voltage output
Current
output
Note 6)
Note 8)
Instantaneous flow
Accumulated flow
–25 to 525 L/min
Instantaneous flow
(Displays [0] when value is within –4 to 4 L/min range.)
Accumulated flow
Instantaneous flow
Accumulated flow
2 MW or more (50 VDC measured via megohmmeter) between terminals and housing
Rc thread
NPT thread
G thread
PFMC7102
Dry air, N
(Air quality grade is JIS B 8392-1 1.1.2 to 1.6.2, ISO 8573-1 1.1.2 to 1.6.2.)
0 to 50°C
Thermal type
10 to 1000 L/min
10 to 1050 L/min
0 to 999,999,990 L
1 L/min
Interval of 2 or 5 minutes can be selected.
0 to 0.8 MPa
1.2 MPa
Refer to "Pressure Loss" graph.
±5% F.S. (0 to 0.8 MPa, 0.6 MPa reference)
12 to 24 VDC ±10%
Ripple (p-p) 10% or less
55 mA or less
Polarity protection
±3% F.S.
±3% F.S.
±1% F.S. (±2% F.S. when response time is set to 0.05 seconds.)
±5% F.S. (0 to 50°C, 25°C reference)
NPN open collector
PNP open collector
Select from Normal or Reversed output.
28 VDC
NPN output type: 1 V or less (at load current 80 mA)
PNP output type: 1.5 V or less (at load current 80 mA)
Select from 0.05 sec., 0.1 sec., 0.5 sec., 1 sec., or 2 sec.
Variable from 0
Short circuit protection
Voltage output: 1 to 5 V, Current output: 4 to 20 mA
Output impedance: Approx. 1 kW
Maximum load impedance at power supply voltage 24 V: 600 W,
at power supply voltage 12 V: 300 W
Minimum load impedance: 50 W
Linked with the response time of the switch output.
Input voltage: 0.4 V or less (Reed or Solid state) for 30 msec. or longer
Accumulated flow external reset, Peak/Bottom reset
Select from Standard condition or Normal condition.
L/min, cfm (ft
–50 to 1050 L/min
(Displays [0] when value is within –9 to 9 L/min range.)
0 to 999,999,999 L
1 L/min
LCD, 2-screen display (Main screen/Sub screen)
Main screen: Red/Green, Sub screen: White
Main screen: 4 digits, 7 segment, Sub screen: 6 digits, 11 segment
LED ON when switch output is ON. (OUT1/OUT2: Orange)
250 VAC for 1 minute between terminals and housing
Operation: 0 to 50°C, Storage: –10 to 60°C (No condensation or freezing)
Operation, Storage: 35 to 85% RH (No condensation or freezing)
CE, UL (CSA), RoHS
Rc1/2, NPT1/2, G1/2
Stainless steel 304, PPS, Aluminum alloy, HNBR, Si, Au, GE4F
160 g
170 g
+25 g
rate changes from 0 to the maximum flow instantaneously) until the
switch output turns ON (or OFF) when set at 90% of the rated flow rate.
Note 4) If the flow fluctuates around the set value, the width for setting more than
the fluctuating width needs to be set. Otherwise, chattering will occur.
Note 5) Setting is only possible for models with analog output.
Note 6) The time from when the flow is changed as a step input (when the flow
rate changes from 0 to the maximum flow instantaneously) until the
analog output reaches 90% of the rated flow rate.
Note 7) Setting is only possible for models with external input.
Note 8) The flow rate given in the specification is the value at standard
condition.
Note 9) Setting is only possible for models with the unit selection function.
2
10 L
10 L/pulse
80 mA
3
/min)
L, ft
3
–100 to 2100 L/min
(Displays [0] when value is within –19 to 19 L/min range.)
10 L
IP65
Rc3/4, NPT3/4, G3/4
+80 g
PFMC7202
20 to 2000 L/min
20 to 2100 L/min
240 g
245 g
+30 g