Lennox Merit CBX25UH Series Installation Instructions Manual page 11

Table of Contents

Advertisement

BLOWER RELAY
NOTE — Refer to wiring diagram located on the unit access panel (or figure 13 above) and blower performance (table 2).
S
All air data measured external to unit with 1 inch non-pleated air filter in place.
S
All factory settings are medium speed except the -48 which is set to low speed from the factory.
S
All data given while air handler is operating with a dry DX coil.
Table 2. CBX25UH Blower Performance (3-Speed PSC) - 240V (CFM @ ESP. - in. W. C.)
Air Handler
Blower Speed
Model
Low (Red)
Med (Blue)
18
High (Black)
Low (Red)
Med (Blue)
24
High (Black)
Low (Red)
30
Med (Blue)
High (Black)
Low (Red)
36
Med (Blue)
High (Black)
Low (Red)
42
Med (Blue)
High (Black)
Low (Red)
Med (Blue)
48
High (Black)
Low (Red)
Med (Blue)
60
High (Black)
S
Blower Performance (CFM vs. ESP inches H2O)
S
Cooling speeds should not be reduced below factory setting.
S
Units with electric heat approved at 0.5" maximum and medium blower speed minimum.
CHANGING BLOWER SPEED
5
BLOWER RELAY
HARNESS
BLUE (MED)
2
4-PIN
BLOWER CONNECTOR
Figure 13. Changing Blower Speed
.10" WC
.20" WC
510
495
670
650
905
865
630
625
885
875
1130
1100
900
865
1075
1060
1240
1210
1160
1140
1500
1445
1660
1575
1325
1315
1490
1465
1820
1770
1775
1710
1995
1895
2070
1970
1675
1630
1965
1925
2140
2085
Page 11
PLASTIC CAPS
RED (L0)
BLACK (HI)
YELLOW (COM)
.30" WC
.40" WC
475
630
820
615
850
1070
1010
830
1030
1170
1135
1115
1085
1385
1300
1495
1405
1300
1275
1440
1395
1690
1600
1645
1565
1800
1685
1850
1719
1580
1520
1875
1800
2000
1895
.50" WC
420
325
595
505
770
705
610
580
820
780
950
780
740
985
940
1085
990
1200
1390
1225
1315
1500
1470
1560
1595
1450
1695
1795
CBX25UH SERIES

Advertisement

Table of Contents
loading

Table of Contents