Technical specifications
Technical specifications of the DI 16X24VDC HA
Article number
General information
Firmware version
•
Usable terminal block
Color code for module-specific color identifica‐
tion plate
Product function
•
Engineering with
•
•
•
•
Operating mode
•
Redundancy
•
Supply voltage
Rated value (DC)
permissible range, lower limit (DC)
permissible range, upper limit (DC)
Reverse polarity protection
Input current
Current consumption (rated value)
Current consumption, max.
Encoder supply
Output voltage, min.
Output current
•
•
24 V encoder supply
•
DI 16x24VDC HA
Equipment Manual, 10/2020, A5E39265608-AD
FW update possible
I&M data
STEP 7 TIA Portal configurable/integrated
from version
STEP 7 configurable/integrated from version
PCS 7 configurable/integrated from version
PROFINET from GSD version/GSD revision
DI
Redundancy capability
up to 60 °C, max.
up to 70 °C, max.
24 V
6DL1131-6BH00-0PH1
V1.0
Yes
TB type H1, M1 and N0
CC01
Yes; I&M0 to I&M3
V16
V5.6
V9.0
GSDML V2.3
Yes
Yes; With TB type M1
24 V
19.2 V
28.8 V
Yes
60 mA; without sensor supply
120 mA; without sensor supply
18.2 V; L+ (-1 V)
2 A; 1 A when mounted vertically; see derating in‐
formation in Equipment Manual
1 A; See derating information in Equipment Manual
Yes
8