Input Wiring; Control Output Wiring - Honeywell Pro-Watch 6000 Installation Manual

Two-reader module
Hide thumbs Also See for Pro-Watch 6000:
Table of Contents

Advertisement

Installing the PW-6000 Two-Reader Module
Wiring

Input Wiring

Inputs 0 to 7 may be configured to use normally open or normally closed contacts and non-supervised
or supervised (with standard ±1% tolerance 1K ohm). Four of these inputs have default functional
definitions, but all eight can be configured to monitor general-purpose sensors.
By default, Input 0 is defined as the Door Status Input corresponding to reader 0 and Input 1 is defined
as the REX input corresponding to reader 0. Also by default, Input 2 is defined as the Door Status
Input corresponding to reader 1 and Input 3 is defined as the REX input corresponding to reader 1.
Inputs 4, 5, 6 and 7 are general purpose inputs that can be used to monitor sensors or as control inputs.
Inputs 6 and 7 are not accessible when the board is rack mounted.
Inputs TMP and PFL are typically used for monitoring cabinet tamper and power failure respectively.
These two inputs are not supervised and are not accessible when the board is rack-mounted. These
inputs were primarily provided for the case when this board is mounted remotely and cannot take
advantage of the tamper and power fail detect inputs on the controller board. If these inputs are not
used, install a short piece of wire at the input to indicate safe condition.
Input configuration including debounce and hold time is set via host software.

Control Output Wiring

Six form-C relay contacts are provided for controlling door strike or other devices. Each may be
assigned to door-related functions or general-purpose output. They are configurable as standard
(energize to activate) or fail-safe (de-energize to activate) via host software.
The energized or ON time of each relay can be configured using Pulse control for single or repeating
pulses via host software. The energized or ON time for a single pulse can be extended up to 24 hours.
For repeating pulses, the on/off time can be defined in 0.1 second increments and be repeated up to 255
times.
Relays 0 and 2 are rated for and normally used to control the door locks associated with readers 0 and
1 respectively. While Relays 0 and 2 are sized to handle the typical loads generated by electrical locks,
load switching can cause abnormal contact wear and premature contact failure. Switching of inductive
loads (i.e., strike) also causes EMI (electromagnetic interference) which may interfere with normal
operation of other equipment. To minimize premature contact failure and to increase system reliability,
a contact protection circuit is highly recommended. The following two circuits are suggested. Locate
the protection circuit as close to the load as possible (within 12 inches [30cm]); the effectiveness of the
circuit decreases as the distance from the load increases.
12
www.honeywell.com

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pw6k1r2

Table of Contents