Installing The Pw-6000 Two-Reader Module; Description - Honeywell Pro-Watch 6000 Installation Manual

Two-reader module
Hide thumbs Also See for Pro-Watch 6000:
Table of Contents

Advertisement

Installing the PW-6000 Two-Reader
Module

Description

The PW-6000Two-Reader Module provides support for up to two access control doors
by providing connections for Wiegand or Clock/Data type readers, supervised inputs,
and relay outputs. You can either mount the board in a rack or open and flat. If you
rack-mount the board, only one edge is accessible for wiring; however, a flat mount
increases the amount of available I/O slightly but significantly decreases the number
of boards that can be mounted in one enclosure.
The I/O terminals are organized to support two doors. Starting at the bottom of the
rack-mount side of the board, the first connector provides power to the board. The
next connector provides communication with the Intelligent Controller (PW6K1IC or
PW5K1IC). The next set of terminals connects reader 1. The next set of terminals
connects the I/O typically associated with reader 1, namely the Door Status and REX
status inputs and the Door Lock and Lock Status relay outputs. Continuing up this
edge the next two connectors provide the reader and associated I/O terminals for
reader 0. The last connector on the rack-mount edge provides terminals for two
additional general-purpose inputs.
When the board is mounted flat, two additional relay outputs and two additional
general-purpose inputs are available along with two dedicated inputs for cabinet
tamper and power fault detection on the opposite edge of the board.
The reader interface accepts a Wiegand signal of Data 1 and Data 0 or a Clock and
Data signal and provides 5VDC or 12VDC reader power, a tri-stated LED control and
buzzer control. Two of the six form-C relay outputs are sized for the inductive load of
door locks and the other four are designed to handle dry-circuit signals. All of the
inputs are capable of four-state supervision except the two dedicated inputs.
Communication to the control panel is accomplished via an RS-485 interface. This
board requires 12VDC input power.
When communication to the control panel is lost, this board can grant access based on
facility code only. General purpose outputs will retain the setting at the time
communication was lost. Up to eight facility codes may be active in each PW6K1R2
or PW5K1R2. Keypad input must follow the reader input format and is in place of or
multiplexed with the reader data.
PW-6000 Two-Reader Module Installation Guide, Document 800-01951, Revision C
1

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pw6k1r2

Table of Contents