Alarm Indicators - Omron K8AC-H Manual

Digital heater element burnout detector
Hide thumbs Also See for K8AC-H:
Table of Contents

Advertisement

Nomenclature
■ Nomenclature and Operations
Up key
Down key

Alarm Indicators

Order of
Alarm
7-segment
priority
display
characters
hbt1
1
Heater burnout 1
hbt2
2
Heater burnout 2
3
SSR open circuit
ssro
ssrs
4
SSR short circuit
hrs1
5
Heater layer short
1
hrs2
6
Heater layer short
2
Note: 1. As soon as the cause of an alarm is removed, the alarm is
reset automatically.
2. If multiple alarms occur simultaneously, the one with the
highest priority is displayed.
3. If the mode is changed to ADJ or SET mode while an alarm
is in effect, the alarm output is reset and the ALM and SSR
indicators turn OFF.
Operation indicators
Main display area
Shift key
Mode key
Level key
LED
Alarm contents
indicator
ALM
CT1 heater
indicator lit
burnout detected.
ALM
CT2 heater
indicator lit
burnout detected.
SSR
SSR open circuit
indicator lit
detected (when
heater current
cannot be
detected with
temperature
control gate output
ON).
SSR
SSR short circuit
indicator lit
detected (when
heater current is
detected with
temperature
control gate output
OFF).
ALM
CT1 overcurrent
indicator lit
detected.
ALM
CT2 overcurrent
indicator lit
detected.
Name
Main display
Displays processing values, parameter characters,
and set values.
Oper-
RUN (Mea-
Lights when the power is turned ON and the
ation
surement
measurement operation is in progress.
indi-
operation)
OFF at all other times.
cators
ADJ
Lights while in adjust mode.
(Adjust)
Flashes while in test mode.
OFF at all other times.
SET (Set)
Lights while in set mode.
OFF at all other times.
GATE
Lights or turns OFF according to gate input status.
(Gate)
Gate pulse: Lights for high voltage pulse; OFF for
Gate linear: Lights for 4 mA or over; OFF for less
SSR
Lights when an SSR error occurs (open or short
(SSR error)
circuit).
(See note.)
OFF when SSR is normal.
ALM
Lights for heater burnout or overcurrent.
(Alarm)
OFF at all other times.
(See note.)
Up key
Increments a set value when the set value is in
change status.
Down key
Decrements a set value when the set value is in
change status.
Shift key
Used to check set values while parameters are
displayed, and to put set values in change status.
Used to shift the set value digit when the set value is
in change status.
Mode key
Used to switch the displayed parameter.
Level key
Used to change the level.
Note: Check the specific status using the alarm display parameters
on the main display.
Processing Value Display Ranges and
Functions
Processing
Display
Display
value name
characters
range
ct 1
Heater 1
0100 to 2300
current
(See notes 1
and 2.)
ct 2
Heater 2
0100 to 2300
current
(See notes 1
and 2.)
Note: 1. The decimal point position depends on the input type.
K8AC-H@1@@: 0.100 to 2.300
K8AC-H@2@@: 1.00 to 23.00
K8AC-H@3@@: 10.0 to 230.0
2. If the display is below 0100, the bar display "----" will be
shown.
K8AC-H
Operation
low voltage pulse.
than 4 mA.
Unit
Function
A
This is the CT1 heater
current processing value.
Alarm operations such as
the heater burnout alarm
are determined based on
this processing value.
A
This is the CT2 heater
current processing value.
Alarm operations such as
the heater burnout alarm
are determined based on
this processing value.
14