Gas burner control

Advertisement

Technical data
General unit data
Environmental
conditions
6/11
Building Technologies Division
For technical data – with the exception of the data listed below and the switching times of
the switching mechanism – refer to Data Sheet N7451.
Perm. length of detector cable
Normal cable, laid separately
Shielded cable, shielding connected to
terminal 22, e.g. high-frequency cable
Capacity
Output on startup (without fan
assistance)
Nominal output
Storage
Climatic conditions
Mechanical conditions
Temperature range
Humidity
Transport
Climatic conditions
Mechanical conditions
Temperature range
Humidity
Operation
Climatic conditions
Mechanical conditions
Temperature range
Humidity
Installation altitude
Warning!
Condensation, formation of ice and ingress of water are not permitted!
If not observed, there is a risk of impairment of safety functions and of
electric shock hazard.
Max. 50 m
Max. 100 m
Any (with ignition < 120 kW)
Any
DIN EN 60721-3-1
Class 1K3
Class 1M2
-20...+60 °C
<95% r.h.
DIN EN 60 721-3-2
Class 2K2
Class 2M2
-40...+60 °C
<95% r.h.
DIN EN 60 721-3-3
Class 3K5
Class 3M2
-20...+60 °C
<95% r.h.
Max. 2,000 m above sea level
CC1N7454en
20.11.2017