Wiring - Weil-McLain 2 Series Manual

Hide thumbs Also See for 2 Series:
Table of Contents

Advertisement

series
GV90+
Gas piping
Natural Gas
1. Refer to Figure  65 for pipe length and diameter. Size gas
supply piping for total flow to all connected appliances.
For each GV90+ boiler, provide for the following gas flow
(cfh = cubic feet per hour):
Boiler model
GV90+3
GV90+4
GV90+5
GV90+6
2. Inlet pressure required at gas valve inlet:
maximum 14" w.c.
minimum 3.5" w.c.
Install 100% lockup gas pressure regulator in sup-
ply line if inlet pressure exceeds 14" water column.
Adjust for 14" w.c. maximum.
Propane Gas
1. Contact gas supplier to size pipes, tanks and 100% lockup
gas pressure regulator.
2. Adjust propane supply regulator provided by gas supplier for
14" w.c. maximum pressure.
3. Inlet pressure required at gas valve inlet:
maximum 14" w.c.
minimum 5" w.c.
Figure 65
Pipe capacity for 0.60 specific gravity natural gas
Capacity in cubic feet of gas per hour
Natural gas only, with specific gravity of 0.60
Based on pressure drop of 0.3" w.c.
Gas pipe
length
(feet)
½"
¾"
10
132
278
20
92
190
30
73
152
40
63
130
50
56
115
75
45
93
100
38
79
150
31
64
For additional gas pipe sizing information, refer to ANSI Z223.1/NFPA
54 - latest edition (or Natural Gas and Propane Installation Code, B149.1
or B149.2 for Canadian installations).
Part number 550-143-010/1021
gas-fired water boiler – boiler manual
2
(continued)
CFH natural gas
70
105
140
175
Gas pipe diameter —
1"
1¼"
1½"
520
1050
1600
350
730
1100
285
590
860
245
500
760
215
440
670
175
360
545
150
305
460
120
250
380

Wiring

For your safety, turn off electrical power supply at
service entrance panel before making any electrical
connections to avoid possible electric shock hazard.
Failure to do so can cause severe personal injury or
death.
Installation must comply with:
National Electrical Code and any other national, state, provincial
or local codes or regulations. In Canada, CSA C22.1 Canadian
Electrical Code Part 1, and any local codes. Boiler must be elec-
trically grounded as required by National Electrical Code ANSI/
NFPA 70 - latest edition.
Wiring must be NEC Class 1. Boiler must be elec-
trically grounded as required by National Electrical
Code ANSI/NFPA 70 - latest edition.
To replace wiring, order complete harness assem-
blies from Weil-McLain. If any original wiring as
supplied with boiler must be replaced, and a har-
ness is not immediately available, use only type
105°C wire or equivalent. Use this wiring only as a
temporary repair. Obtain a complete harness from
Weil-McLain.
Wiring connections
Power wiring
Connect 120 VAC power wiring as shown in Figure 66, page 56.
The junction box is located on the inside left jacket panel.
Watch the polarity of the circuit when connect-
ing the 120 VAC power wiring. If the polarity is
switched, the integrated boiler control will lockout.
The IBC will flash the POWER light to indicate
this problem. See the troubleshooting information
beginning on page 76.
Additional limit controls
Wire additional limit controls (if used) as shown in
ure 67, page 56.
Thermostat(s)
Install thermostats on inside walls, away from influences of
drafts, hot or cold water pipes, lighting fixtures, television, sun
rays, or fireplaces.
Follow instructions with thermostat. If it has a heat anticipator,
set heat anticipator in thermostat to match power requirements
of equipment connected to it (ignition control and gas valve, zone
valve contacts, etc.). Wiring diagram on boiler gives setting for
standard equipment (ignition control and gas valve).