Installation Patterns - Daikin Altherma 3 R ECH2O Installation Manual

Hide thumbs Also See for Altherma 3 R ECH2O:
Table of Contents

Advertisement

4.1.3

Installation patterns

Depending on the type of room in which you install the indoor unit, different installation patterns are allowed:
Room type
Living room, kitchen, garage, attic, basement, storage room
Technical room (i.e. room that is NEVER occupied by persons)
b
a
Ventilation openings
Minimum floor area
Chimney
Release in case of
refrigerant leakage
Restrictions
A
Room A (= room where indoor unit is installed)
B
Room B (= adjacent room)
a
If no chimney is installed, this is the default point of release
in case of refrigerant leakage.
If needed, you can connect a chimney here:
▪ Unit's connection point for the chimney = 1" male thread.
Use a compatible counterpart for the chimney.
▪ Make sure the connection is airtight.
b
Chimney
c1
Bottom opening for natural ventilation
c2
Top opening for natural ventilation
H
Actual release height:
release
1a 2a
: Without chimney. From floor to top of the unit.
▪ For 300 l units => H
release
▪ For 500 l units => H
release
1b 2b
: With chimney. From floor to top of the chimney.
▪ For 300 l units => H
release
▪ For 500 l units => H
release
3a
Installation with chimney connected to the outside. The
release height is not relevant. There are no requirements to
the minimum floor area.
N/A
Not applicable
EBSH/X(B)11+16P30+50DF
Daikin Altherma 3 R ECH₂O
4P663483-1A – 2021.11
PATTERN 1
A
A
b
1b
1a
N/A
Between room A and B
Room A
Room A + Room B
Might be needed
Might be needed
Inside room A
1" [ 4  11],
See
"PATTERN
"PATTERN
"Tables for PATTERN 1, 2 and
=1.89 m
=1.90 m
=1.89 m + Chimney height
=1.90 m + Chimney height
PATTERN 2
PATTERN 3
B
A
b
b
c2
3a
2b
2a
c1
Connected to outside
Inside room A
Outside
2" [ 4  11],
3" [ 4  13], and
"PATTERN
3" [ 4  13]
Minimum floor area / Release height:
▪ The minimum floor area requirements depend on the release
height of the refrigerant in case of a leakage. The higher the
release height, the lower the minimum floor area requirements.
▪ The default point of release (without chimney) is at the top of the
unit. To decrease the minimum floor area requirements, you can
increase the release height by installing a chimney. If the chimney
leads outside of the building, there are no requirements anymore
to the minimum floor area.
▪ You can also take advantage of the floor area of the adjacent
room (= room B) by providing ventilation openings between the
two rooms.
▪ For installations in technical rooms (i.e. room that is NEVER
occupied by persons), additionally to patterns 1, 2 and 3, you can
also use PATTERN 4. For this pattern there are no requirements
to the minimum floor area if you provide 2 openings (one at the
bottom, one at the top) between the room and the outside to
ensure natural ventilation. The room must be protected from frost.
When connecting a chimney
▪ Install the chimney socket (delivered as accessory) to the plate
heat exchanger box.
4 Unit installation
Allowed patterns
1, 2, 3
1, 2, 3, 4
PATTERN 4
A
c2
c1
N/A
Between room A and
outside
N/A
N/A
N/A
Inside room A
See
"PATTERN
Installation manual
4" [ 4  15]
9