6.2
Cables for power supply and Ethernet
Cable specification
The following table lists the requirements for a cable depending on the use case.
Application
Direct 24 V DC supply
Power supply adapter 12 to 24 VDC
Power supply adapter 100 to 240 VAC
Ethernet
Fiber-optic cable multimode
(for device variants with optical connectors)
SCALANCE W786-x
Operating Instructions, 12/2021, A5E03678337-14
6.2 Cables for power supply and Ethernet
Specification
•
Round cable cross-section with
6 to 8 mm diameter.
Two-wire cable with 0.5 to 1.5 mm
per wire.
•
Permitted tensile load at least
100 N.
•
UL listing: Type PLTC or ITC
•
Round cable cross-section with
6 to 8 mm diameter.
Two-wire cable with 0.5 to 1.5 mm
per wire.
•
Permitted tensile load at least
100 N.
•
UL listing: Type PLTC or ITC
•
Round cable cross-section with
6 to 8 mm diameter.
•
Three-core cable with 0.5 - 1.5 mm
of the individual cores.
•
Permitted tensile load at least
100 N.
1. IE FC TP standard cable GP 2 x 2 (Type A)
article no.: 6XV1840-2AH10
2. IE TP Torsion Cable 2 x 2 (Type C)
Article number: 6XV1870-2F
3. IE FC TP Trailing Cable 2 x 2 (Type C)
Article number: 6XV1840-3AH10
UL listing: Type PLTC or ITC (the three named types
have this approval)
FO Standard Cable GP
Article number: 6XV1873-2A
Minimum bending radius 65 mm.
You can find detailed information on preassembled ca‐
ble lengths and connectors in the catalog "IK PI".
FO Robust Cable GP 2G50/125/900
Article number: 6XV1873-2R
Halogen-free, UV-resistant cable for indoors and out‐
doors for ambient temperatures ‑40 °C ... +70 °C.
Connecting up
cross-section
2
2
cross-section
cross section
2