8 Adapting the unit to the heating installation
8.2

Setting the maximum heating output

The unit's maximum heating output can be adjusted to the
system's heat demand. Use diagnostics code D.000 to set a
value that corresponds to the output in kW.
8.3
Setting the pump overrun and pump
operating mode
You can set the pump overrun under D.001 (default setting:
5 min.).
You can use diagnostics code D.018 to set the pump operat-
ing modes Eco or Comfort.
In Comfort mode, the internal pump is switched on when the
heating flow temperature is not at Heating off ( Operating
instructions) and the heating requirement is enabled via an
external control.
Eco (default setting) is useful for removing residual heat
after hot water generation when the heat demand is ex-
tremely low and large target temperature spreads exist
between the hot water generation and heating mode target
values. This prevents living rooms from being under-sup-
plied. If there is a heat demand, the pump is switched on
every 25 minutes for 5 minutes once the overrun time has
elapsed.
8.4

Setting the maximum flow temperature

You can use diagnostics code D.071 to set the maximum
flow temperature for heating mode (default setting: 75 °C).
8.5

Setting the return flow temperature control

If the product is connected to an underfloor heating system,
the temperature control setting can be changed from flow
temperature control (default setting) to return flow temperat-
ure control using diagnostics code D.017.
8.6

Burner anti-cycling time

8.6.1
Setting the burner anti-cycling time
To prevent frequent switching on and off of the burner and
thus prevent energy losses, an electronic restart lockout
is activated for a specific period each time the burner is
switched off. You can adjust the burner anti-cycling time to
the conditions of the heating installation. The burner anti-
cycling time is only active for the heating mode. Hot water
handling mode during a burner anti-cycling time does not af-
fect the time function element. You can use diagnostics code
D.002 to set the maximum burner anti-cycling time (default
setting: 20 min.). The effective burner anti-cycling times with
respect to the target flow temperature and the maximum set
burner anti-cycling time can be found in the following table:
T
Set maximum burner anti-cycling time [min]
Flow
(target)
1
5
[°C]
30
2.0
4.0
35
2.0
4.0
40
2.0
3.5
45
2.0
3.0
50
2.0
3.0
55
2.0
2.5
60
2.0
2.0
28
10
15
20
25
8.5
12.5
16.5
20.5
7.5
11.0
15.0
18.5
6.5
10.0
13.0
16.5
6.0
8.5
11.5
14.0
5.0
7.5
9.5
12.0
4.5
6.0
8.0
10.0
3.5
5.0
6.0
7.5
T
Set maximum burner anti-cycling time [min]
Flow
(target)
1
[°C]
65
2.0
70
2.0
75
2.0
T
Set maximum burner anti-cycling time [min]
Flow
(target)
35
[°C]
30
29.0
35
25.5
40
22.5
45
19.5
50
16.5
55
13.5
60
10.5
65
7.0
70
4.0
75
1.0
Note
The remaining burner anti-cycling time following a
regular shutdown in heating mode can be called
up under diagnostics code D.067.
8.6.2
Resetting the remaining burner anti-cycling
time
1st option
Menu → Reset anti-cycl. time
The current burner anti-cycling time appears in the display.
Confirm the burner anti-cycling time reset by pressing
(Select).
2nd option
Press the fault clearance key.
8.7

Setting the maintenance interval

If you set the maintenance interval, after a configurable num-
ber of burner operating hours, the message that the product
must be serviced appears in the display together with the
maintenance symbol
the information Maintenance MAIN.
Set the operating hours until the next maintenance using
diagnostics code D.084. Guideline values can be found in
the following table.
Number
30
Heat de-
of per-
mand
25.0
sons
22.0
1 ‑ 2
5.0 kW
19.5
2 ‑ 3
17.0
1 ‑ 2
10.0 kW
14.0
2 ‑ 3
11.5
2 ‑ 3
15.0 kW
9.0
3 ‑ 4
Installation and maintenance instructions auroCOMPACT 0020233500_01
5
10
15
20
1.5
2.5
3.5
4.5
1.5
2.0
2.5
2.5
1.0
1.0
1.0
1.0
40
45
50
33.0
37.0
41.0
45.0
29.5
33.0
36.5
40.5
26.0
29.0
32.0
35.5
22.5
25.0
27.5
30.5
18.5
21.0
23.5
25.5
15.0
17.0
19.0
20.5
11.5
13.0
14.5
15.5
8.0
9.0
10.0
11.0
4.5
5.0
5.5
6.0
1.0
1.0
1.0
1.0
. The eBUS controller display shows
Burner operating hours until the
next inspection/maintenance work
is due (dependent upon the sys-
tem type)
1050 h
1150 h
1500 h
1600 h
1800 h
1900 h
25
30
5.5
6.5
3.0
3.5
1.0
1.0
55
60
49.5
44.0
38.5
33.0
28.0
22.5
17.0
11.5
6.5
1.0