Siemens RUGGEDCOM WIN7225 Installation Manual page 48

Table of Contents

Advertisement

Chapter 5
Certification
Standard
IEC 60068-2-6
Power Input
IEC 61000-4-11
EMC
IEC 61000-4-12
IEC 61000-4-4
IEC 61000-4-3
IEC 61000-4-2
Insulation
IEC 60255-5 (6.1.3)
IEC 60255-5 (6.1.4)
Military Standard Tests
Test
MIL-STD-810F
40
Method
IEEE 1613 (10)
IEEE 1613 (10)
IEEE 1613 (5.1)
IEEE 1613 (7.3.1)
IEEE C37.90.1
IEEE 1613 (7.3.2)
IEEE C37.90.1
IEEE 1613 (8)
Radiated Susceptibility Immunity
IEEE C37.90.2
IEEE 1613 (9)
IEEE C37.90.3
IEEE 1613 (6.3
IEEE 1613 (6.2)
Description
Salt Fog
Description
Shock (Drop)
Vibration
Voltage Variations
Oscillatory SWC
Fast Transient SWC
ESD
HV Impulse
Dielectric
RUGGEDCOM WIN7225
Installation Guide
Test Levels
1 m (3.3 ft), 1 Fall per Axis
2
2 g (32 ft/s
), 10-150 Hz per Axis
38.4 to 56 V
2.5 kV
4 kV
80 MHz to 1 GHz
20 V/m (unmodulated)
35 V/m (modulated)
8 kV Contact, 15 kV Air
5 kV
Test Levels
Method 509.4
EMC and Environmental Type Tests

Advertisement

Table of Contents
loading

Table of Contents