Bradford White URG2PV50T6N Manual page 13

Power vent gas water heater
Table of Contents

Advertisement

Venting (Part I) continued-
Table 2 lists the venting distances allowed with 4" (10.2 cm) diameter vent pipe.
When venting with 4" (10.2 cm) vent pipe, use a 4" (10.2 cm) to 3" (7.6 cm)
reducer to exit through the building wall with 3" (7.6 cm) vent pipe. Use the 3"
(7.6 cm) vent terminal supplied with the water heater to terminate on the
outside of the building. If the length of 3" (7.6 cm) vent pipe needed to go
through the wall is greater than 14" (35.5 cm), use 4" (10.2 cm) to go through
the wall and reduce to 3" (7.6 cm) vent pipe immediately after exiting the
outside wall. Refer to the venting illustrations on the following pages. Make
sure the vent pipe terminal elbow fitting is at least 1" (2.5 cm) away from the
edge of the wall.
Terminating
Through the Wall
Through the Wall
Through the Wall
Through the Wall
Through the Roof
Through the Roof
Through the Roof
Through the Roof
Terminating
Through the Wall
Through the Wall
Through the Wall
Through the Wall
Through the Wall
Through the Roof
Through the Roof
Through the Roof
Through the Roof
Through the Roof
TABLE 1 - VENT CONNECTOR LENGTHS
FOR 3" (7.6 cm) DIAMETER VENT PIPE
# of Elbows
1
2
3
4
0
1
2
3
TABLE 2 -VENT CONNECTOR LENGTHS
FOR 4" (10.2 cm) DIAMETER VENT PIPE
# of 90
Elbows (excl.
vent term.)
1
2
3
4
5
0
1
2
3
4
Maximum straight
Length ft (m)
48, 65 gal.
55 (16.8)
50 (15.2)
45 (13.7)
40 (12.2)
60 (18.3)
55 (16.8)
50 (15.2)
45 (13.7)
Maximum straight
Length ft (m)
48, 65 gal.
175 (53.3)
170 (51.8)
165 (50.3)
160 (48.8)
155 (47.2)
180 (54.9)
175 (53.3)
170 (51.8)
165 (50.3)
160 (48.8)
13
Minimum
straight
Length
ft (m)
2 (.6)
2 (.6)
2 (.6)
2 (.6)
7 (2.1)
7 (2.1)
7 (2.1)
7 (2.1)
Min
straight
Length
ft (m)
10 (3.1)
10 (3.1)
10 (3.1)
10 (3.1)
10 (3.1)
15 (4.6)
15 (4.6)
15 (4.6)
15 (4.6)
15 (4.6)