Toshiba MMD-AP0186HP1-E Service Manual page 73

Table of Contents

Advertisement

Check code
Outdoor 7-segment display
Main
remote
Check
Sub-code
controller
code
H14
H14
H15
H15
Location
Description
System status
of
detection
I/F
Compressor 2
All stop
case thermo
activation
I/F
TD2 sensor
All stop
miswiring
(incomplete
insertion)
73
Error detection
Check items (locations)
condition(s)
Compressor 2 case
Check Compressor 2 case thermo
thermo was
circuit.
activated.
(Connector, Wiring, Circuit board)
Open and check the service valve.
(Gas side, Liquid side)
Check the outdoor PMV clogging
(PMV1, 2).
Check the SV42 circuit.
Check the SV4 circuit (SV41 / 42
miswiring).
Check the opening status of indoor
PMV.
Check the four-way valve error.
Check the refrigerant shortage.
Air discharge
Check installation of TD2 sensor.
temperature of (TD2)
Check connection of TD2 sensor connector
does not increase
and wiring.
despite compressor
Check resistance characteristics of TD2
2 being in operation.
sensor.
Check for defect in outdoor P.C. board (I/F).